5-6
Comparing and Merging EtherCAT
Network Configurations
5-6-1
Introduction for Comparing and Merging EtherCAT Network
Configurations
Use the Sysmac Studio to compare the network configuration information settings in the Sysmac Stu-
dio with the actual network configuration that is connected, including branch locations of a branching
topology.
The following items are compared.
• Node Addresses
• Vendor IDs
• Product codes
• Revisions
• Connection ports
If the settings in the Sysmac Studio and the actual network configuration match completely, it is possi-
ble to identify the locations of errors when they occur.
If differences are shown in the comparison results, merge the configurations from the Sysmac Studio.
Network Configuration Settings
on the Sysmac Studio
#10
#13
#15
Out1
Out2
Out3
#15
#13
#10
Out1
Out2
Out3
#11
#14
#12
#11
#12
#14
#09 (Junction Slave)
Input port
“#” indicates a node address.
Output port
#09 (Junction Slave)
Actual Network Configuration
That Is Connected
The output port numbers for the branches do not match the node addresses for the connected
slaves. In this example, the settings on the Sysmac Studio and the slaves connected to Out1 and
Out3 on node #09 in the actual network configuration do not match.
5-6-2
Operation Procedure for Comparing and Merging EtherCAT Net-
work Configurations
Use the following procedure to compare and merge the network configuration settings on the Sysmac
Studio and the actual network configuration.
5 Setting Up EtherCAT Communications with the Sysmac Studio
5-28
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Содержание NJ101-10 Series
Страница 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 68: ...2 Part Names and Slave Settings 2 18 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Страница 279: ......