5-6 Gro
undin
g
Grounding has the following two purposes.
• Protective Grounding
Protective grounding is done to ensure safety. It is intended to prevent electrical shock by holding the
electrical potential at the grounding potential that is generated by factors such as leakage, induction,
or failure.
• Functional Grounding
Functional grounding is done to protect device and system functions, including prevention of noise
from external sources, or prevention of noise from devices or equipment that could have harmful
effects on other devices or equipment.
The functional ground must in some cases be determined by experimentation. It is important to suffi-
ciently check the particular circumstances before grounding.
Wiring the Ground
The NA unit has a protective ground terminal (
) and a functional ground terminal (
).
1. Protective Ground
For safety, be sure to use a ground of 100
Ω
or less for the protective ground of the NA unit. For
the grounding wiring, refer to
• Applicable Wire
• Screw Tightening Torque
1.0 to 1.2 N·m
3-5-6
Grounding
Grounding Methods and Precautions
Conductor cross-section
2.00 mm
2
min.
24VDC
24VDC
+
-
Protective ground terminal
SD
SD
SD
Содержание NA-series
Страница 8: ...Sections in this Manual 6 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 12: ...CONTENTS 10 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 82: ...3 Installation and Wiring 3 22 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 164: ...5 Troubleshooting 5 18 NA series Programmable Terminal Hardware V1 User s Manual V125 ...
Страница 179: ...I 1 I NA series Programmable Terminal Hardware V1 User s Manual V125 Index ...
Страница 181: ......