Table 12-2 DIP Switch Fault Codes
Code Displayed
System Status
Corrective Action
20
Incorrect operating mode or
floating blanking switch setting.
1. Check setting of operating mode
switches 1 and 2.
2. Check setting of floating blanking
switches 5 and 6.
21
Invalid switch setting.
1. Check to see that settings of switch
positions 1 through 7 are valid and
identically set between switches A and B.
22
DIP switch settings changed during
operation.
1. Press and release start switch or cycle
power.
23
Invalid switch settings.
1. Check channel select and MPCE
switches for valid settings.
Table 12-3 Safety Output (OSSD) Faults
Code Displayed
System Status
Possible Cause/Corrective Action
30
General safety output (OSSD) fault.
1. OSSD A shorted to OSSD B. Check
wiring. Wiring according to manual.
2. OSSD A or OSSD B shorted to power.
Check wiring. Wire according to manual.
3. OSSD A or OSSD B shorted to ground.
Check wiring. Wire according to manual.
Table 12-4 MPCE Faults
Code Displayed
System Status
Corrective Action
40
General MPCE fault.
1. Possible incorrectly wired MPCE circuit.
Check and wire according to manual.
41
MPCE Open before safety output
(OSSD) activation.
1. Check to confirm that MPCE circuit is
closed before OSSD activation.
43
MPCE open when power is applied.
1. Check to confirm that MPCE circuit is
closed when power is applied.