97
7.
Troubleshooting
7.1 Warnings
Warnings come as errors and alarms. The types of errors and alarms are described below.
* If you intend to meter negative values (exported energy), then no correction is necessary. Metering continues normally even
when a warning is displayed. If the warning is not needed, go to "Warning for negative reactive power value ON/OFF (MENU
0A)" and set to OFF
62).
To cancel the alarm, take the actions described to remove the cause, then restart the product or switch the power on again.
Warning type
Description
Display
Action to take
Error
Setting value error
Internal memory corrupted
Contact the place of purchase or
the manufacturer.
Measured value
error
Internal memory corrupted
Calibration value
error
Calibration value is corrupted
Alarm
Input frequency
warning
Measured frequency is outside
rated ranges
Input the power and voltage with
the frequency within the rated
ranges.
VR phase warning
The voltage has not reached the
rated value
Wire correctly.
VS phase warning
VT phase warning
Phase sequence
error
The phase sequence is incorrect
for 1-phase 3-wire, 3-phase 3-wire,
or 3-phase 4-wire connection
Wire correctly.
Active power is a
negative value
Active power is a negative value
(The voltage and current phase
may not match due to incorrect
wiring)
Check the wiring, and correct it if
there is anything inappropriate. *
OUT1
Output warning
• Pulse is output again while a
pulse is being output
• Pulse is output during a period
when the pulse is off
Change the pulse output unit so
that pulses are not output while
other pulses are being output.
OUT2
Output warning
OUT3
Output warning
OUT4
Output warning