Single-phase Current Relay

 

K8AB-AS

Cat. No. N142-E1-02

2.

Hysteresis

Hysteresis is set using the hysteresis knob (HYS.)
The setting range is 5 to 50% of the operating value.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the 
same level.)
Use this as a guide to set the hysteresis.
Example: Maximum of 200 A AC, Current Setting (SV) of 50%, and Overcurrent Operation

Operation will be at 100 A and resetting at 90 A when the hysteresis (HYS.) is set to 10%.

3.

Operating Time

The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the 
same level.)
Use this as a guide to set the operating time.
If the input current exceeds (drops lower than) the current setting, the alarm indicator will start flashing for the set period and then stay lit.

4.

Startup Lock Time

The startup lock time is set using the startup lock time knob (LOCK).
The startup lock time can be set to between 0 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes 
(when the set value and the input have reached the same level.)
Use this as a guide to set the startup lock time.
The startup lock time will start when the input current reaches 30% or more of the current 
setting.
Use startup lock time to prevent unwanted operation, e.g., as a result of inrush current.

Dimensions

(Unit: mm)

Single-phase Current Relays

OMRON CT

Inrush current

Current setting

30% of current setting

Startup lock timer start

Startup lock time

There are no outputs 
during this period.

22.5

100

72

90

5

5

K8AB-AS1
K8AB-AS2
K8AB-AS3

1.8

76

4.1

10

10

5.9

5.2

20

Two M5 screw holes or 
two 5.5-dia. holes

57

30 dia.

14.5

14.5

6

8.5

50

33.5

34.5

81.5

13.5

86

54

63

11

4.7

Four M4 

×

 6 screws

17

20

9.3

1.7

1.7

9.3

76

Mounting Hole Dimensions

Note:

The OMRON Current Transformer (CT) is 
designed to be used with the K8AB-AS3. 
Use terminals k and l for connections.
(Terminals kt and lt are not used.)

K8AC-CT200L

Содержание K8AB-AS

Страница 1: ...Commercial CT input signal 0 to 1 A 0 to 5 A supported Output status can be monitored using LED indicator Model Number Structure Model Number Legend 1 Basic Model K8AB Measuring and Monitoring Relays...

Страница 2: ...1 to 1 A AC DC 0 5 to 5 A AC DC 0 8 to 8 A AC DC 24 VDC not insulated K8AB AS2 24 VDC See note 1 24 VAC insulated K8AB AS2 24 VAC 100 115 VAC insulated K8AB AS2 100 115 VAC 200 230 VAC insulated K8AB...

Страница 3: ...ely 30 or more of the set value Note Enabled only for overcurrent operation Indicators Power PWR Green Relay output RY Yellow Alarm outputs ALM Red Input impedance Refer to the Input Range on the prev...

Страница 4: ...luence Operating value Based on ambient humidity of 65 25 to 80 5 max Operating time Based on ambient room humidity 25 to 80 10 max Influence of power supply voltage Operating value 5 max Operating ti...

Страница 5: ...current path if the inputs and power supply are connected to the same line T LOCK Hysteresis 5 to 50 of operating value Lit Flashing T Operating time 0 1 to 30 s Lock Startup lock time 0 to 30 s Oper...

Страница 6: ...K Alarm indicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when re...

Страница 7: ...method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit K8AB AS does not use SW1 Setting Method 1 Setting Current The current knob SV is used to se...

Страница 8: ...for the set period and then stay lit 4 Startup Lock Time The startup lock time is set using the startup lock time knob LOCK The startup lock time can be set to between 0 and 30 s Turn the knob while t...

Страница 9: ...s 2 Make sure to use setting values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner o...

Страница 10: ...ply are connected internally so the K8AB AS will not operate normally if an unwanted current path exists If an unwanted current path exists use a K8AB model with an AC power supply or use an isolated...

Страница 11: ...rating value 25 operating time 0 1 s startup lock timer 0 1 to 30 s set according to the duration of the startup current The K8AB AS3 can be set to between 10 to 100 of the rated current 10 A to 100 A...

Страница 12: ...ice of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS W...

Отзывы: