Cat. No. N142-E1-02

Single-phase Current Relay

 K8AB-AS

11

For a 5 A motor, the startup current would be approximately 
30 A. The startup current would thus exceed the overload 
capacity of the K8AB-AS1 or K8AB-AS2 (150% of rated 
current for 1 s). 
It is thus necessary to use the K8AB-AS3 to monitor a motor 
load. (K8AB-AS3 overload capacity: 120% of rated current 
continuously, 200% of rated current for 30 s, and 600% of 
rated current for 1 s)
The K8AB-AS3 has a wide input range, so wind the wire 
around the CT several times.

Reason for Winding the Wire around the CT 
Used with the K8AB-AS3

Example: Monitoring Overloads for a Motor Rated at 5 A

K8AB Settings

Overcurrent detection, operating value: 25%, operating time: 0.1 s, 
startup lock timer: 0.1 to 30 s (set according to the duration of the 
startup current)

The K8AB-AS3 can be set to between 10% to 100% of the rated 
current (10 A to 100 A). The wire is wound five times around the CT 
so that a current of 10 A or greater will flow. This will make the input 
current to the K8AB 5 A/winding x 5 windings, or 25 A. 
If there is a startup current that is 6 times the rated current, the 
startup current would be 25 A 

×

 6, or 150 A (i.e., 150% of the rated 

current). The overload capacity of the K8AB-AS3 is 200% of the 
rated current for 30 s, so the K8AB-AS3 would not fail even if the 
startup current continued for 30 s, enabling overload detection.

500%

100%

Motor current (as percentage of r

ated current)

Several seconds to 
several tens of seconds

Time from beginning of startup

To the K8AB-AS3

Primary side conductor

K8AC-CT200L

Содержание K8AB-AS

Страница 1: ...Commercial CT input signal 0 to 1 A 0 to 5 A supported Output status can be monitored using LED indicator Model Number Structure Model Number Legend 1 Basic Model K8AB Measuring and Monitoring Relays...

Страница 2: ...1 to 1 A AC DC 0 5 to 5 A AC DC 0 8 to 8 A AC DC 24 VDC not insulated K8AB AS2 24 VDC See note 1 24 VAC insulated K8AB AS2 24 VAC 100 115 VAC insulated K8AB AS2 100 115 VAC 200 230 VAC insulated K8AB...

Страница 3: ...ely 30 or more of the set value Note Enabled only for overcurrent operation Indicators Power PWR Green Relay output RY Yellow Alarm outputs ALM Red Input impedance Refer to the Input Range on the prev...

Страница 4: ...luence Operating value Based on ambient humidity of 65 25 to 80 5 max Operating time Based on ambient room humidity 25 to 80 10 max Influence of power supply voltage Operating value 5 max Operating ti...

Страница 5: ...current path if the inputs and power supply are connected to the same line T LOCK Hysteresis 5 to 50 of operating value Lit Flashing T Operating time 0 1 to 30 s Lock Startup lock time 0 to 30 s Oper...

Страница 6: ...K Alarm indicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when re...

Страница 7: ...method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit K8AB AS does not use SW1 Setting Method 1 Setting Current The current knob SV is used to se...

Страница 8: ...for the set period and then stay lit 4 Startup Lock Time The startup lock time is set using the startup lock time knob LOCK The startup lock time can be set to between 0 and 30 s Turn the knob while t...

Страница 9: ...s 2 Make sure to use setting values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner o...

Страница 10: ...ply are connected internally so the K8AB AS will not operate normally if an unwanted current path exists If an unwanted current path exists use a K8AB model with an AC power supply or use an isolated...

Страница 11: ...rating value 25 operating time 0 1 s startup lock timer 0 1 to 30 s set according to the duration of the startup current The K8AB AS3 can be set to between 10 to 100 of the rated current 10 A to 100 A...

Страница 12: ...ice of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS W...

Отзывы: