4 Monitoring the Temperature in Control Panel with the Main Unit and the Software Tool
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
4-1 M
etho
d
o
f Mo
nito
ring
the
T
em
p
erat
ure in t
h
e C
o
n
trol Pan
el
4
4-
1-4 Mon
itor
ing U
sing Softwa
re
Too
ls
When monitoring with the transistor outputs, the following monitoring is available.
The following can be monitored on each screen when monitoring of the temperature in the control panel
is performed with the software tool.
•
Device List of K6PM
Screen: Monitoring of each Main Unit
•
Monitoring K6PM
Screen: Monitoring of each infrared thermal sensor
•
Monitoring sensor
Screen: Monitoring of each segment
When you start the software tool, the following
Select the project
Dialog Box is displayed.
Click the
Create
Button or the
Open
Button.
If you click the
Open
Button, a window for selecting the existing project is displayed. Select a project file
and then click the
Open
Button.
The following
Device List of K6PM
Screen is displayed.
You can perform monitoring for each Main Unit.
Monitor with the Transistor Outputs
Transistor
Output 1
Transistor
output 2
Transistor
output 3
Status
Meaning
ON
*1
*1. This is the output result when "Transistor output type" is set to "Normally closed". By default, it is set to "Nor-
mally closed". By setting it to "Normally open" with the software tool or communications, ON/OFF can be re-
versed.
ON
*1
ON
*2
*2. ON/OFF cannot be reversed for transistor output 3.
Comprehensive
alarm: Normal
All measured values are in normal condi-
tion.
OFF
*1
ON
*1
ON
*2
Comprehensive
alarm: Threshold 1
exceeded
This is the state when there is no "Thresh-
old 2 exceeded" in the measured value,
and there is at least one "Threshold 1
exceeded".
OFF
*1
OFF
*1
ON
*2
Comprehensive
alarm: Threshold 2
exceeded
This is the state when there is at least one
"Threshold 2 exceeded" in the measured
value.
OFF
OFF
OFF
Main Unit error and
K6PM-TH sensor
error occurrence
This is the state when a Main Unit error and
K6PM-TH sensor error has occurred.
4-1-4
Monitoring Using Software Tools
Monitoring of each Main Unit (Device List of K6PM Screen)
Click either one.
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......