6 Monitoring and Setting with the Modbus TCP
6 - 8
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
6-3
Register Address Lists
Registers that can be read and written using Modbus TCP are as follows.
Offset address (hexadecimal)
Contents (communications area)
R/W
0000 to 0004 hex
Main Unit monitor
R
0010 to 9A3F hex
K6PM-TH sensor temperature monitor
1 to 31
R
A000 to A023 hex
Main Unit setting
R/W
A100 to BF41 hex
K6PM-TH sensor alarm setting
1 to 31
R/W
C000 to C019 hex
Product information
R
C200 to C208 hex
IP address
R/W
D000 to D005 hex
Operation command
W
6-3-1
Main Unit Monitor
Address
Parameter
name
Description
Number of
bytes
R/W
*1
*1. R: Read using Reading of multiple registers (03 hex).
0000 hex
Main Unit status
Status of the Main Unit
Refer to "Main Unit status" in
Main Unit Monitor Object (Class ID:
374 hex)
2
R
0001 hex
Running time
data
Running time ratio
0 to 100% (0000 hex to 0064 hex)
2
R
0002 hex
Software version Software version
2
R
0003 hex
Number of con-
nected
K6PM-TH sen-
sors
0 to 31 (0000 to 001F hex)
2
R
0004 hex
Target sensor in
position adjust-
ment mode
0: No target position adjustment
sensor
1: K6PM-TH sensor 1 position
adjustment mode
:
31: K6PM-TH sensor 31 position
adjustment mode
(0000 to 001F hex)
2
R
0005 hex
000E hex
Reserved
0000 hex is returned.
18
R
000F hex
Illegal address
Exception code 02 hex (illegal data
address) is returned.
----
----
Содержание K6PM-TH
Страница 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Страница 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Страница 197: ......