CSM_K3HB-X_DS_E_12_4

1

Process Indicator

K3HB-X

A Process Indicator Ideal for Discriminating and 

Displaying Measurements for Voltage/Current 

Signals

• Easy recognition of judgement results using color display that can be 

switched between red and green. 

*

• Equipped with a position meter for monitoring operating status trends.
• External event input allows use in various measurement and discrimina-

tion applications.

• Series expanded to include DeviceNet models.
• Short body with depth of only 95 mm (from behind the front panel), or 97 

mm for DeviceNet models.

• UL certification approval (Certification Mark License).
• CE Marking conformance by third party assessment body.
• Water-resistant enclosure conforms to NEMA 4X (equivalent to IP66).
• Capable of high-speed sampling at 50 times per second (20 ms)
• Easy-to-set two-point scaling allows conversion and display of any user-

set values.

*

Visual confirmation of judgement results is not supported on models that do not have 

an output or models that do not support DeviceNet.

You can change the display color by setting it, but you cannot switch it based on the 

judgement results.

Model Number Structure

Model Number Legend

Base Units and Optional Boards can be ordered individually or as sets.

Base Units

1. Input Sensor Code

VD: DC voltage input
AD: DC current input
VA: AC voltage input
AA: AC current input

5. Supply Voltage

100-240 VAC: 100 to 240 VAC
24 VAC/VDC: 24 VAC/VDC

Base Units with Optional Boards

2. Sensor Power Supply/Output Type Code

None: None

CPA: Relay output (PASS: SPDT) + Sensor power supply 

(12 VDC +/

10%, 80 mA) (See note 1.)

L1A: Linear current output (0 to 20 or 4 to 20 mA DC) + Sensor power supply 

(12 VDC +/

10%, 80 mA) (See note 2.)

L2A: Linear voltage output (0 to 5, 1 to 5, or 0 to 10 VDC) + Sensor power supply 

(12 VDC +/

10%, 80 mA) (See note 2.)

A:  Sensor power supply (12 VDC +/

10%, 80 mA)

FLK1A: Communications (RS-232C) + Sensor power supply 

(12 VDC +/

10%, 80 mA) (See note 2.)

FLK3A: Communications (RS-485) + Sensor power supply 

(12 VDC +/

10%, 80 mA) (See note 2.)

Note: 1.

CPA can be combined with relay outputs only.

2.

Only one of the following can be used by each Digital Indicator: 

RS-232C/RS-485 communications, a linear output, or 

DeviceNet communications.

Optional Board

Sensor Power Supply/Output Boards

Relay/Transistor Output Boards

Event Input Boards

3. Relay/Transistor Output Type Code

None: None
C1: Relay contact (H/L: SPDT each)
C2: Relay contact (HH/H/LL/L: SPST-NO each)
T1: Transistor (NPN open collector: HH/H/PASS/L/LL)
T2: Transistor (PNP open collector: HH/H/PASS/L/LL)
BCD 

*

: BCD transistor output (NPN open collector: HH/H/PASS/L/

LL)

DRT: DeviceNet (See note 2.)

*

 A Special BCD Output Cable (sold separately) is required.

4. Event input Type Code

None: None
1: 5 inputs (M3 terminal blocks), NPN open collector

*

: 8 inputs (10-pin MIL connector), NPN open collector

3: 5 inputs (M3 terminal blocks), PNP open collector

*

: 8 inputs (10-pin MIL connector), PNP open collector

*

 There is no bank selection for "None" and "DeviceNet" types of "Transistor

Output Type Code".

Note:

The following combinations are not possible.

• Communications (FLK

@

A) + DeviceNet (DRT)

• Communications (FLK

@

A) + BCD output (BCD)

• Linear current/voltage (L

@

A) + DeviceNet (DRT)

Refer to 

Safety Precautions for All Digital Panel 

Meters

.

For the most recent information on models that have been certified for 
safety standards, refer to your OMRON website.

1

K3HB-X

@

5

1

2 3 4

K3HB-X

@

-

@@@

5

2

K33-

@

3

K34-

@

4

K35-

@

Содержание K3HB-X

Страница 1: ...1 L1A Linear current output 0 to 20 or 4 to 20 mA DC Sensor power supply 12 VDC 10 80 mA See note 2 L2A Linear voltage output 0 to 5 1 to 5 or 0 to 10 VDC Sensor power supply 12 VDC 10 80 mA See note...

Страница 2: ...tup compensa tion timer input NPN open collector or no voltage contact signal ON residual voltage 2 V max ON current at 0 4 mA max Max applied voltage 30 VDC max OFF leakage current 0 1 mA max Hold in...

Страница 3: ...m s2 for relay outputs 3 times each in 3 axes 6 directions Weight Approx 300 g Base Unit only Degree of protection Front panel Conforms to NEMA 4X for indoor use equivalent to IP66 Rear case IP20 Term...

Страница 4: ...nal CT current transformer 4 The K3HB XVA complies with UL standards when the applied input voltage is within the range 0 to 150 VAC If the input voltage is higher than 150 VAC install an external tra...

Страница 5: ...at 250 VAC 5 A at 30 VDC 1 A at 250 VAC 1 A at 30 VDC Mechanical life expectancy 5 000 000 operations Electrical life expectancy 100 000 operations Maximum load voltage 24 VDC Maximum load current 50...

Страница 6: ...ne Communications distance Baud rate Network length max Drop line length max Total drop line length max 500 Kbps 100 m 100 m 6 m 39 m 250 Kbps 100 m 250 m 6 m 78 m 125 Kbps 100 m 500 m 6 m 156 m The v...

Страница 7: ...yed Used to switch level Used to switch the display between the PV maximum value and minimum value and to reset the maximum and minimum values PV display SV display Position meter SV display status in...

Страница 8: ...ote Leave 20 ms min between DATA VALID turning OFF and the REQUEST signal See note See note See note Programmable Controller Connection Example Digital Indicator SYSMAC Programmable Controller DC Inpu...

Страница 9: ...C 80 mA 12 VDC 80 mA 10 VDC 100 mA 10 VDC 100 mA Sensor power supply communications Sensor power supply Sensor power supply K33 CPB K33 CPA K33 B K33 A K33 L2B K33 L1B K33 L2A K33 L1A RS 485 K33 FLK3B...

Страница 10: ...re also available E Analog Input D Event Input D6 3 9 k 4 7 k S TMR D2 HOLD D3 RESET D4 ZERO D5 12 V COM D6 D1 750 560 TIMING 12 V COM Models with Terminal Blocks K35 1 K35 3 Models with Connectors K3...

Страница 11: ...atus Turns the comparative output OFF until the measurement value enters the PASS range Average processing of input signals with extreme changes or noise smooths out the display and makes control stab...

Страница 12: ...r red to green The current display value can be selected from the present value the maximum value and the minimum value It is possible to specify i e restrict the values that the smallest dis played d...

Страница 13: ...Higher Lower Output HH Output PASS Output H Output L Output LL Measurement value Higher Lower Measurement value Higher Lower Comparative set value HH Comparative set value H Comparative set value L C...

Страница 14: ...cutout in the panel 2 Insert watertight packing around the Unit to make the mounting watertight 3 Insert the fixture into the grooves on the left and right sides of the rear case and push until it rea...

Страница 15: ...turn OFF the power 19 Use the specified cables for the communications lines and stay within the specified DeviceNet communications distances Refer to the User s Manual Cat No N129 for details on comm...

Страница 16: ...e running lines along separate ducts and using shield lines Example of Countermeasures for Inductive Noise on Input Lines 4 If a noise filter is used for the power supply check the voltage and current...

Страница 17: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Отзывы: