Appendices
Appendices
A-2
Specifications
■
Ratings
*1 For models with DC power supply, approximately 1 A of control power supply capacity is required for
each Digital Indicator. Be sure there is adequate power supply capacity when using more than one
Digital Indicator. We recommend the S8VS DC Power Supply from OMRON.
*2 Models with PNP inputs are also available.
*3 Only the enclosed DeviceNet connector can be used with K3HB models with DeviceNet
communications. The enclosed crimp terminals are for Thin Cable.
*4 Depends on the model.
Power supply voltage
100 to 240 VAC, 24 VAC/VDC, DeviceNet power supply: 24 VDC
Allowable power supply voltage
range
85% to 110% of the rated power supply voltage
DeviceNet power supply: 11 to 25 VDC
Power consumption
(at maximum load)
*1
100 to 240 VAC: 18 VA max., 24 VAC/VDC: 11 VA/7 W max.
Current consumption
DeviceNet power supply: 50 mA max. (24VDC)
Inputs
No-voltage contact, voltage pulse, open collector
External power supply
12 VDC ± 10% 80 mA (only for models with external power supply)
10 VDC ± 5% 100 mA (only for models with external power supply)
Event
inputs
*2 *4
Startup
compensation
timer input
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0
Ω
: 4 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
Hold input
Reset input
Compensation
input
Bank input
Outputs
*4
Relay contact
outputs
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations,
Electrical life expectancy: 100,000 operations
Transistor
outputs
Maximum load voltage: 24 VDC, Maximum load current: 50 mA,
Leakage current: 100
µ
A max.
Linear outputs
0 to 20 mA DC, 4 to 20 mA:
Load: 500
Ω
max, Resolution: Approx. 10,000, Output error: ±0.5% FS
0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC
Load: 5 k
Ω
max, Resolution: Approx. 10,000, Output error: ±0.5% FS (but ±0.15 V, 0 V for 1 V
or less)
Display method
• Negative LCD (backlit LCD) display
• 7-segment digital display (Character height: PV: 14.2 mm (green/red);
SV: 4.9 mm (green)
Main functions
*4
Scaling, measurement operation selection, average processing, previous average comparison,
output hysteresis, output ON delay, output test, teaching, display selection, display color
switching, key protection, bank selection, display refresh period, maximum/minimum hold, reset
Ambient operating temperature
−
10 to 55°C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Storage temperature
−
25 to 65°C (with no icing or condensation)
Altitude
2,000 m max.
Accessories
Waterproof packing, 2 fixtures, terminal cover, unit stickers, instruction manual, DeviceNet
connector (DeviceNet models only, Hirose HR31-5.08P-5SC (01)), crimp terminals (DeviceNet
models only, Hirose HR31-SC-121)
*3
Содержание K35-2
Страница 2: ......
Страница 24: ...Outline Section 1 Outline 1 8 ...
Страница 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Страница 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Страница 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Страница 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Страница 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Страница 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Страница 185: ......