7 - 3
7 GRT1-ECT Installation
GX-series EtherCAT Slave Unit User’s Manual
7-1 In
st
a
lling
an Eth
erCA
T
Netwo
rk
7
7-1
-2 Commu
nication Cables and Conne
ctor
s -
Prep
ar
ation
Prepare the required cables.
Use 100BASE-TX shielded twisted pair cables, category 5 or higher.
The cables should be double-shielded (aluminum tape and braided shielding).
Precautions for Correct Use
•
The maximum cable length between connected nodes is 100 m. Note that some cables do not
guarantee 100 m. In general, if the conductors are strand wire, the transmission performance
will be lower than solid wire and the operation at 100-m distance cannot be guaranteed.
Confirm details with the cable manufacturer.
•
When selecting connectors, check that the cables to be used conform to connectors. Items to
be checked include conductor size, conductor wire type (solid wire/twisted wire, 2/4 pairs), and
outer diameter.
7-1-2
Communication Cables and Connectors - Preparation
Содержание GRT1-ECT SmartSlice
Страница 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Страница 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...