30
Wiring
Section 3-3
1,2,3...
1.
When alarm output 1 or alarm output 2 is reset (i.e., the power turns ON or
the initial setting level is exited), the alarm output will be inactive for 1 sec-
ond. Allow for this in the system design when using an alarm output.
2.
If you connect a contact relay or any device containing a coil to the alarm
output, wire a diode in parallel with the relay coil, as shown in the figure.
■
Operation Selection Input
■
Reset Input
Number of event inputs
2 event inputs
Contact input conditions
ON: 1 k
Ω
max.
OFF: 100 k
Ω
min.
Non-contact input conditions
ON residual voltage: 1.0 V min.
OFF leakage current: 0.1 mA max.
Current flow
Approx. 1.1 mA (per input)
1 s max.
Power ON
Alarm
G3PW Power
Controller
AC power supply
ALARM 1/2
Operation for NO
Contacts
ALARM 1/2
Operation for NC
contacts
Alarm output
Alarm output
inactive period
inactive period
X
X
7. Alarm output 1 (+)
8. Alarm output 1 (
−
)
9. Alarm output 2 (+)
10. Alarm output 2 (
−
)
1
2
3
4
5
6
7
8
9
10
11. Event input (+)
12. Event input (
−
)
13
14
Automatic
Manual
1
2
3
4
5
6
7
8
9
10
11
12
13. Reset input (+)
14. Reset input (
−
)
Содержание G3PW
Страница 1: ...Cat No Z280 E1 01 User s Manual G3PW Power Controllers...
Страница 2: ...G3PW Power Controllers User s Manual Produced November 2008...
Страница 3: ...iv...
Страница 15: ...xvi...
Страница 49: ...34 Wiring for Specific Applications Section 3 4...
Страница 61: ...46 Setting Parameters in the Initial Setting Level Section 4 6...
Страница 77: ...62 Heater Burnout Detection Section 5 9...
Страница 113: ...98 Parameter Settings in the Adjustment Level Appendix B...
Страница 117: ...102 Index...
Страница 119: ......