19
F3SJ-A
User’s Manual
Chapter1
Ratings
Overview and Specifications
E
Response time (ON to OFF) :Response time of 1st unit + Response time of 2nd unit + Response time
of 3rd unit
-
5 (ms)
Response time (OFF to ON) :Response time (ON to
OFF) x 5 (ms)
When 4 sets are series-connected:
Response time (ON to OFF) :Response time of 1st unit + Response time of 2nd unit + Response time
of 3rd unit + Response time of 4th unit
-
8 (ms)
Response time (OFF to ON) :Response time (ON to OFF) x 5 (ms)
Cable Extension Length
Total extension length must be within a length specified by the table below, including length of series
connection cable.
When there is no relay unit, or when power is supplied from an external power source
When connected to F3SP-B1P
Extension of the cable must be within a specified length. If it isn't, safety function may not work
properly, resulting in danger.
Condition
Single
2 connected
3 connected
4 connected
Incandescent display lamps are
used by auxiliary output and/or
external indicator output
45m
40m
30m
20m
Incandescent display lamps are
not used
100m
60m
45m
30m
Condition
Single
2 connected
3 connected
4 connected
Incandescent display lamps are
- used by external indicator
output 2
40m
30m
25m
20m
Incandescent display lamps are
- used by external indicator
output 1
and/or,
- used by auxiliary output 1
60m
45m
30m
20m
Incandescent display lamps are
not used
100m
60m
45m
30m