Wiring Examples
Some examples of a motor control system using F3SJ are shown. The category of these systems defined by
EN954-1 is 4.
Connecting to an F3SP-B1P
•Reduced wiring due to connector connection
•Safety relay included
PLC
IN1
IN2
OUT
S1
S2
A1
H1
L1
J1
H1
X1
P1
13
23
33
41
KM3
KM1
KM2
OSSD1
OSSD2 K1
K2
K1
K2
A2
PE
T31
T32
14
24
34
42
KM1
KM2
KM1
KM2
E1
+DC24V
0V
M
Emitter
Receiver
Interlock
selection
Test
Reset
Auxiliary
output
External device
monitoring
Model F3SP-B1P
- Manual reset mode
- Using external device monitoring function
S1
:External test switch
S2
:Interlock/lockout reset switch
KM1, KM2 :Magnetic contactor
KM3
:Solid state contactor (G3J)
M :3-phase
motor
E1
:24VDC power supply (S82K)
PLC :Programmable
controller
(Used for monitoring not related to safety system)
Model F39-JC B-L
Model F39-JC B-D
Unblocked
Blocked
External test switch (S1)
Reset switch (S2)
Safety output
K1,K2 N.O. contact
KM1,KM2 N.O. contact
K1,K2 N.C. contact
KM1,KM2 N.C. contact
PLC input
PLC input
PLC output