55
F3SG-SR
User’s Manual
Chapter
2
External Device Monitoring (EDM)
System Operation and Functions
E
Timing chart
2-11-2. Factory Default Setting
The EDM function is disabled.
2-11-3. Setting with Intelligent Tap
The user can select the setting from EDM Enabled or Disabled by the DIP Switch. When enabling
EDM, the function operates under the following condition.
• Allowable delay time *: 0.3 s (factory default setting)
* By using SD Manager 3, this parameter can be set by 0.1 s in a range of 0.1 to 4.0 s.
Make sure the Position 2 of the DIP Switch is set at ON (DIP Switch Enabled) to activate the settings by the DIP Switch.
After making the setting, make sure to perform the wiring so that the specified voltage is supplied into the RESET line of
the receiver without passing through the NC contacts of the external relays, and confirm the F3SG-SR enters the
LOCKOUT state.
ON
OFF
ON
OFF
T1
Lockout
T1 max.
T1: Allowable delay time. This parameter can be set by 0.1 s in a range of 0.1 to 4.0 s.
Unblocked
Blocked
Beam state
OSSD
EDM
Содержание F3SG-SR Series
Страница 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Страница 18: ...xvi Introduction F3SG SR User s Manual...
Страница 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Страница 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Страница 360: ...332 Chapter 6 Connectable Safety Control Units F3SG SR User s Manual Input Output Circuit and Applications...
Страница 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Страница 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...