System Operation and Functions
2-7. External Test
2-7-1. Overview
This function stops the emission using an external signal. It can be used to verify that a safety system
should properly stop (safety output turns OFF) when F3SG-RA is blocked.
To stop the emission, apply the following voltage to the emitter's TEST input line according to the DIP
switch settings of the emitter.
When muting, safety output is kept ON even if the emission is stoped.
The External Test is not available for the F3SG-RE.
<Basic wiring diagram>
F3SG-RA Series
X
F3SG-RE Series
DIP Switch settings
(Position 4 on Emitter)
24 V Active
0 V Active
Input voltage
9 V to Vs
0 to 3 V
㻱㼙㼕㼠㼠㼑㼞
㻱㼙㼕㼠㼠㼑㼞
24 V Active
0 V Active
+24 VDC
Power Supply
S1: Test Switch
(Connect the line to
0 V if this switch is not required)
S1: Test Switch (Connect the line to
24 V if this switch is not required)
0 VDC
+24 VDC
Power Supply
0 VDC
24 VDC: Brown
TEST: Black
0 VDC: Blue
24 VDC: Brown
TEST:
Black
0 VDC: Blue
S1
S1
F39-JG
A-L
F39-JG
A-L
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...