92
Chapter
2
Warn
in
g Zone
F3SG-R
User’s Manual
System Operation and Functions
2-17-2. Factory Default Setting
The factory default setting is Warning Zone Disable.
2-17-3. Setting with DIP Switch
The user cannot make any changes to this function by the DIP Switch.
2-17-4. Setting with Configuration Tool
Some settings of functions configurable with the Configuration Tool may increase risks.
Make sure the Responsible Person conduct a thorough risk assessment analysis before
managing and changing the settings. Unintended changes to the settings may cause a
person to go undetected, resulting in serious injury.
The user can make changes to the settings by the Configuration Tool.
If you want to output the light unblocked/blocked states of the warning zone, configure the output
operation mode of the auxiliary output or Lamp as warning zone information.
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Refer to
Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User’s Manual
for more
information on setting this function by the Configuration Tool.
Function
Factory Default Setting
Available Parameters
Warning zone
Disable
Disable/Enable from upper/Enable from lower
Zone setting
None
Any beam from top beam/any beam from
bottom beam
Содержание F3SG-RA
Страница 1: ...F3SG R Series Safety Light Curtain User s Manual Cat No Z352 E1 08 http www ia omron com f3sg r...
Страница 16: ...xiv Introduction F3SG R User s Manual...
Страница 24: ...xxii Introduction F3SG R User s Manual...
Страница 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Страница 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Страница 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Страница 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...