F3SG-SR/PG
User’s Manual
Chapter
6
Wiring Exa
m
p
le
s
(f
or F3
SG-SR/PG)
Input/Output Circuit and Applications
E
6-2-1-10. Single Break with EDM and Intelligent Tap
[Wiring Example (F3SG-SR)]
• When using the Intelligent Tap (F39-SGIT-IL3) with the emitter and receiver connected, the following functions are not available.
- External Test
- Operating Range Selection by wiring
- Optical Synchronization
• When a functional earth is necessary, wire an earth cable according to the example in
6-2-1-1. Auto Reset Mode with Optical
Synchronization and EDM Unused
. Also refer to
5-4-4. Functional Earth Connection
for more information.
F3SG-SRA
F3SG-PGA-A/-L
F3SG-SRB
F3SG-PGA-C
Timing chart
Reset s
w
itch (S1)
Press position s
w
itch (S2)
OSSD
T1: Minim
u
m pressing time of reset s
w
itch.
Config
u
ra
b
le from 100 to 500 ms in 100-ms
increments
b
y SD Manager 3.
T2: Minim
u
m
b
reak time (300 ms)
T3: Minim
u
m pressing time of press position
s
w
itch. T3 = T1
T4:
W
ait time
u
ntil single
b
reak is complete (30 s
or less)
*
W
hen the machine is stopped
b
y
u
nintended
b
lock in the middle of pressing of parts, operation
of the s
w
itch (S1) and then a single d
u
mmy
b
reak
are needed for reinitiation of the machine cycle.
T1 min. T2 min.
Feeding
parts
T3 min.
T3 min.
T2 min.
T1 min.
T4
Machine stops
Machine restarts
Feeding
parts
Unintended
b
lock
D
u
mmy
b
reak *
Un
b
locked
Blocked
S1
KM1
S2
KM2
F39-SGIT
24 VDC
IO-Link
Master *3
Wiring for NPN *1
24 VDC
F39-JG
□
B-L/
XS5F-D521-DJ0-IL
F39-JG
A-D
F39-JGR3K-L
F39-JGR3K-D
IN
PLC *2
24V/0V (Brown)
Not used (Pink)
PSDI (Gray)
0V/24V (Blue)
OPERATING RANGE
SELECT INPUT (Yellow)
AUX (Red)
OSSD 1 (Black)
OSSD 2 (White)
*4
KM1
KM2
KM1
KM2
M
Cam
S2
Receiver
Emitter
Function
Setting
DIP switch *6
SD Manager 3
EDM
-
[External device monitoring] : Enable
Operating Range Selection *5
-
[Operating Range Selection] : Long mode
-
[Operating Range Selection] : Short mode
PSDI
N/A
[PSDI] : Single break
Non-Muting system
Perform wiring according to the wiring diagram.
N/A
[Muting] : Disable
External Test not used
N/A
Wired Synchronization
Connect the emitter and receiver with the Intelligent Tap.
*1. Reverse the polarity of the power supply when using in the NPN system. Select a PLC of
PNP or NPN type according to the system of your application.
*2. When connecting to the PLC, the output mode must be changed with the SD Manager 3
according to your application. Refer to
Chapter 4 Setting with SD Manager 3
for more
information on setting the functions by the SD Manager 3.
*3. For connecting with the IO-Link Master unit, refer to an instruction manual of the IO-Link
Master unit you use.
*4. This is the case for a PELV circuit.
*5. F3SG-SR and F3SG-PGA-L can be set up in both Long Mode and Short Mode. F3SG-
PGA-A/-C does not support the Operating Range Selection function.
*6. The PSDI is only configurable by the SD Manager 3, not by the DIP Switch.
S1: Reset s
w
itch
S2: Press position s
w
itch
KM1, KM2: Safety relay
w
ith forci
b
ly g
u
ided contacts
(G7SA) or magnetic contactor
PLC: Programma
b
le logic controller (Used for monitoring
only.
N
OT related to safety system.)
M: Motor
Intelligent Tap
Needed
Содержание F3SG-PG Series
Страница 18: ...xvi Introduction F3SG SR PG User s Manual...
Страница 30: ...xxviii Introduction F3SG SR PG User s Manual...
Страница 74: ...44 Chapter 1 List of Models F3SG SR PG User s Manual Overview and Specifications...
Страница 180: ...150 Chapter 2 IO Link F3SG SR PG User s Manual System Operation and Functions...
Страница 226: ...196 Chapter 3 Intelligent Tap Application Example F3SG SR PG User s Manual Setting with Intelligent Tap...
Страница 430: ...400 Chapter 6 Connectable Safety Control Units F3SG SR PG User s Manual Input Output Circuit and Applications...
Страница 438: ...408 Chapter 7 Maintenance Checklists F3SG SR PG User s Manual Checklists...