![Omron ERT1 Series Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/omron/ert1-series/ert1-series_operation-manual_743568070.webp)
50
Screw-less Clamp Terminals
Section 4-2
Dimensions
4-2-3
Thirty-two-point Output Units (with Screw-less Clamps)
ERT1-OD32SLH-1
Output Specifications
Item
Specification
Output points
32 points
Internal I/O common
PNP
Output current
0.5 A/point, 4.0 A/common
Residual voltage
1.2 V max. (0.5 A DC, between each output terminal and
the V terminal)
Leakage current
0.3 mA max. (24 V DC, between each output terminal
and the V terminal)
ON delay
0.5 ms max.
OFF delay
1.5 ms max.
Number of circuits per
common
16 outputs/common
Isolation method
Photocoupler
Output indicators
LED (yellow)
Power supply short-circuit
protection
Operates when output current is exceeded.
Disconnection detection
Operates at current consumption of 3 mA/point max. (Not
detected at 3 mA or less.)
Output handling for com-
munications errors
Select either hold or clear from Network Configurator.
Current consumption
Communications power supply (including internal cir-
cuits): 120 mA max.
Connection forms
Screw-less clamp terminal blocks (yellow)
Mounting
35-mm DIN Track mounting
Weight
485 g max.
Standard accessories
FKMCP1.52STF3.5AUSOO (Phoenix Contacts) (connec-
tor with lock screws)
Содержание ERT1 Series
Страница 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Страница 2: ......
Страница 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ...viii...
Страница 14: ...xiv...
Страница 58: ...38 Recommended Network Devices Section 2 2...
Страница 62: ...42 Basic Specifications of Slave Units Section 3 1...
Страница 78: ...58 Screw less Clamp Terminals Section 4 2...
Страница 92: ...72 Environment resistive Slave Units Section 5 2...
Страница 102: ...82 Maintenance and Replacement Section 7 3...
Страница 106: ...86 Revision History...
Страница 107: ......