2. Specifications
2-14
2.2. Ratings and Performance
Hardware Specifications
2.2.1.
Item
Details
Supply Voltage
100 to 240 VAC 50/60 Hz
Allowable Power Supply Voltage Range
85 to 264 VAC 50/60 Hz
Power Consumption
15VA or less
LAN and
sub-LAN
Ports
2 ports
Interface
10BASE-T/100BASE-TX
Connector
RJ-45
Transmission Rate 10 M/100 Mbps
Type
CSMA/CD
Cascaded Stages 10BASE-T: Up to 4 stages, 100BASE-TX: Up to 2 stages
(for a repeater hub in both)
Transmission
Distance
100 m
Other Functions
Automatic crossover/straight identification
RS-485
Ports
4 ports
Communications
Protocol
CompoWay/F
Maximum
Connections
31 devices for 1 port (total for the device: 31 devices
×
4 ports =
124 devices)
Terminal Resistor Built-in (120
Ω
)
Communication Speed
9.6 k/19.2 k/38.4 kbps (factory shipment: 9.6 kbps)
Data Length
7/8 bits (factory shipment: 7 bits)
Stop Bits
1/2 bits (factory shipment: 2 bits)
Vertical Parity
None/Even/Odd (factory shipment: Even)
General-
Purpose
Input
Inputs
1 input
Function
Pulse input
Input Voltage
10.2 to 26.4 VDC
Input Impedance
Approx. 2.2 k
Ω
Input Current
12 VDC/5 mA (TYP), 24 VDC/10 mA (TYP)
ON Voltage
10.2 VDC or higher
OFF Voltage
5.0 VDC or less
Input Pulse Width 5 ms or longer
General-
Purpose
Output
Count
4 outputs
Function
Monitoring alarm output
Maximum Load Voltage
30 VDC
Maximum Load Current
50 mA/output
ON Resistance
5
Ω
or less
Insulation Resistance (*)
Between power terminals and FG terminal: 20 M
Ω
or higher
(500 VDC)
Between power terminals and general-purpose input, general
purpose outputs #1 to 4, RS-485 communications ports #1 to 4,
LAN, sub-LAN, OPTION1, and OPTION2: 20 M
Ω
or higher
(500 VDC)
Between ground, FG terminal and OPTION1, OPTION2: 20
M
Ω
or higher (500 VDC)
Withstand Voltage (*)
Between power terminals and FG terminal: 1500 VAC for 1
minute
Содержание EQ100-E
Страница 1: ...Sensor Network Server Model EQ100 E User s Manual Catalog No N196 E1 01H ...
Страница 55: ...2 Specifications 2 24 2 5 Dimensions Top View Front View Unit mm ...
Страница 92: ...7 EQ100 Settings 7 3 4 Click OK to view the EQ project setup menu Setting Menu ...
Страница 197: ...9 Web UI Function 9 24 3 In the Save As dialog box enter a destination to save and click Save Download is completed ...