70
Remote I/O Allocations
Section 3-2
3-2
Remote I/O Allocations
3-2-1
I/O Allocations
The DST1-series Safety I/O Terminals internally store I/O data. Connection
paths can be set using the Network Configurator to allocate I/O data for the
Master Unit. Be sure to set the required connection paths.
3-2-2
I/O Data
The DST1-series Safety I/O Terminals store the following data.
•
SAFE
: The Controller can use this information in safety-related functions.
Data
Description
Input data
Safety Input Data
SAFE
ON/OFF value of safety input terminal after input evaluation
0: Input terminal OFF or error
1: Input terminal ON
Combined Safety Input Status
Normal Status Flag for all safety input terminals. Used to monitor safety input termi-
nal errors, such as disconnections, ground faults, and short-circuits.
0: Error for one or more terminals
1: All terminals normal (no error)
Individual Safety Input Status
Normal Status Flag based on evaluation of the safety input terminal. Used to moni-
tor safety input terminal errors, such as disconnections, ground faults, and short-cir-
cuits.
0: Error
1: Normal (no error)
Combined Safety Output Status
Normal Status Flag for all safety output terminals. Used to monitor safety output ter-
minal errors, such as ground faults and short-circuits.
0: Error for one or more terminals
1: All terminals normal (no error)
Individual Safety Output Status
Normal Status Flag based on evaluation of the safety output terminal. Used to mon-
itor safety output terminal errors, such as ground faults and short-circuits.
0: Error
1: Normal (no error)
Muting Lamp Status
Indicates the status when terminal T3 is configured as the muting lamp output.
0: Error
1: Normal (no error)
Safety Output Monitor
Safety output terminal monitored value
0: Output terminal OFF
1: Output terminal ON
Individual Test Output Status
Indicates the status of the test output terminal.
0: Error
1: Normal (no error)
Safety Input Logic Result (DST1-
XD0808SL-1 only.)
SAFE
Operation result for safety input logic operation
0: OFF
1: ON
Reset Required Indication Signal
(DST1-XD0808SL-1 only.)
Reset required indication signal pulse for reset of logic operations.
Содержание DST1-ID12SL-1
Страница 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Страница 2: ......
Страница 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Страница 4: ...iv...
Страница 10: ...x...
Страница 14: ...xiv...
Страница 110: ...86 Remote I O Allocations Section 3 2...
Страница 116: ...92 Indicators Section 4 2...
Страница 134: ...110 DST1 XD0808SL 1 Section 5 4...
Страница 146: ...122 Maintenance Section 7 4...
Страница 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Страница 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Страница 178: ...154 Index...
Страница 181: ...157 Revision History...