63
Editing Parameters
Section 3-1
IMPORTANT
When the Safety Input Channel Mode
is set to
Test Pulse from Test Out,
spec-
ify the test output to use for the test source and set the Test Output Channel
Mode of the test output to
Pulse Test Output.
S
Dual Channel Safety
Input Discrepancy Time
0 to 65,530 ms
(in 10-ms increments)
Sets the time to monitor the logic discrepancy
in the dual channel input logic.
0 ms
I/O Comment
32 characters max.
Sets an I/O comment for the safety input. The
I/O comment set here is used as the I/O tag in
the Logic Editor.
None
Maintenance Counter
Mode Choice
Time (cumulative ON
time monitor)
Sets the operating mode for the maintenance
counter.
Time
Count (contact opera-
tion counter)
Threshold Mainte-
nance Counter
0 to 4,294,967,295
hours
Sets the threshold value for the maintenance
counter.
0
Item
Settings
Description
Default
Содержание DST1-ID12SL-1
Страница 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Страница 2: ......
Страница 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Страница 4: ...iv...
Страница 10: ...x...
Страница 14: ...xiv...
Страница 110: ...86 Remote I O Allocations Section 3 2...
Страница 116: ...92 Indicators Section 4 2...
Страница 134: ...110 DST1 XD0808SL 1 Section 5 4...
Страница 146: ...122 Maintenance Section 7 4...
Страница 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Страница 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Страница 178: ...154 Index...
Страница 181: ...157 Revision History...