50
Wiring
Section 3-3
6.
Do not pull on cables. Doing so may result in disconnection.
7.
Do not bend cables beyond their natural limit. Doing so may result in dis-
connection.
Connectors
Connections to the I/O Connector
Note
A soldered connector is provided with the Unit.
Connections to the Special I/O Connector
Note
A soldered connector is provided with the Unit.
Applicable Connector Terminal Conversion Units
Recommended Wire Size
The recommended size for cable wires is AWG 24 to 26 (0.2 to 0.13 mm
2
).
Use a cable with an outer diameter of less than 1.61 mm.
Wiring Method
1,2,3...
1.
Check that all the Units are mounted securely.
Note
Ensure that pressure is not exerted on cables.
2.
To prevent the wire cuttings that are scattered during wiring from entering
the interior of the Unit, leave the label attached to the top of the Unit when
performing wiring. After wiring has been completed, remove the label to al-
low proper heat dissipation.
Connector type
Number of pins
Ordering as a
set (OMRON)
Ordering individually
(Fujitsu)
Soldered
(See note.)
24 pins
C500-CE241
Socket: FCN-361J024-AU
Connector cover:
FCN-360C024-J2
Crimp
24 pins
C500-CE242
Housing: FCN-363J024
Connector cover:
FCN-360C024-J2
Contact: FCN-363J-AU
Pressure welded
24 pins
C500-CE243
FCN-367J024-AU/F
Connector type
Number of pins
Ordering as a
set (OMRON)
Ordering individually
(Fujitsu)
Soldered
(See note.)
40 pins
C500-CE404
Socket: FCN-361J040-AU
Connector cover:
FCN-360C040-J2
Crimp
40 pins
C500-CE405
Socket: FCN-363J040
Connector cover:
FCN-360C040-J2
Contact: FCN-363J-AU
Pressure welded
40 pins
C500-CE403
FCN-367J040-AU
Connecting Cable
Connector–
Terminal
Conversion Unit
Number of pins
Size
XW2Z-
@@@
B
XW2D-40G6
40 pins
Miniature
XW2B-40G5
Standard
XW2B-40G4
Standard
XW2Z-
@@@
BU
XW2D-40C6
Miniature
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......