33
Contact I/O Specifications (All Units)
Section 2-2
2-2
Contact I/O Specifications (All Units)
2-2-1
Contact I/O Specifications
Item
Specifications
Contact
inputs
Number of inputs
12 inputs
• 4 inputs (input bits IR 00000 to IR 00003) can be used either as interrupt inputs or
normal inputs.
Note
Each of these 4 inputs can be set to be used as either interrupt inputs or normal
inputs in the Unit Setup Area (DM 6620). It is also possible to specify the ON,
OFF, or both for the interrupt timing for each point (Input Interrupt Mode or
Counter Mode) in the Unit Setup Area (DM 6620).
• 8 inputs (input bits IR 00004 to IR 00011) can be used as normal inputs only.
Input voltage/cur-
rent
24 V
+10%
/
–15%
, 5 mA typical
Min. ON voltage
15.2 V
Max. OFF voltage
4.8 V
Input response
Inputs for interrupt input or normal input (4 points with one common):
ON delay time: 50
m
s
OFF delay time: 200
m
s max.
Inputs for normal input (8 points with one common):
ON delay time: 100
m
s
OFF delay time: 1 ms max.
Circuit configura-
tion
Interrupt inputs
Normal inputs
Customizable Counter Unit
Internal circuit
Input
indicator
Input
indicator
Internal circuit
4.7 k
Ω
4.7 k
Ω
750
Ω
750
Ω
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......