24
Performance Specifications
Section 2-1
I/O memory
Input Area
12 bits: IR 000 (IR 00000 to IR 00011)
The Unit’s built-in input points are allocated to these bits (fixed alloca-
tions).
Note
IR 00000 to IR 00003 can be used either as normal input bits
or for interrupt inputs (in Input Interrupt Mode or Counter
Mode).
Output Area
8 bits: IR 001 (IR 00100 to IR 00107)
The Unit’s built-in output points are allocated to these bits (fixed allo-
cations).
Work Area
1,088 bits (68 words): IR 002 to IR 049 (IR 00200 to IR 04915), IR 200
to IR 219 (IR 20000 to IR 21915)
These bits have no specific functions and can only be used in the pro-
gram.
SR Area
568 bits (36 words): SR 220 to SR 255 (SR 22000 to SR 25507)
These bits have specific functions.
Note
SR 230 to SR 234 and words SR 235 to SR 239 are used for
exchanging general-purpose data with the CPU Unit.
AR Area
448 bits (28 words): AR 00 to AR 27 (AR 0000 to AR 2715)
These bits have specific functions.
TR Area
8 bits: TR 0 to TR 7
These bits temporarily store the ON/OFF status of an instruction block
for branching.
LR Area
512 bits (32 words): LR 00 to LR 31
These bits are for exchanging general-purpose data with the CPU
Unit. (Data can be exchanged cyclically with user-set words in the
CPU Unit. Up to 32 words of data can be input or output. The word
allocation are specified in the Unit Setup Area.)
Timer/Counter Area
256 points: TIM/CNT 000 to TIM/CNT 255 (The same numbers are
used for timers and counters.)
When using the CNT and CNTR instructions, at power interruption or
when the mode is switched, present counter values are held (with
super-capacitor backup) at the values immediately before power was
interrupted or the mode was switched. When other instructions are
used, the data in the TIM/CNT Area is cleared.
DM Area
(general-purpose read/write
area)
6,144 words: DM 0000 to DM 6143
Data in this area can be read or written in word (16-bit) units. It is held
(with super-capacitor backup) at power interruptions or when the
mode is switched. Writing can be performed with instructions or from
the Programming Device.
Note
By turning ON bit SR 25200, it is possible to save all the data in
the range DM 0000 to DM 6143 to flash memory. The data is
read using the XFER instruction.
EM Area
2,048 words: EM 0000 to EM 2047
Data in this area can be read or written in word (16-bit) units. It is pos-
sible to specify whether the data is held (with super-capacitor backup)
at power interruptions or when the mode is switched. Writing can be
performed with instructions or from the Programming Device.
Item
Specifications
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......