22
Performance Specifications
Section 2-1
2-1-3
Program and Memory
Effect on CPU Unit’s cycle time
• When data exchange is performed using the words allocated in
the CIO Area only: 0.2 ms
• When data exchange is performed using words allocated in the
DM Area or the LR Area: 0.5 ms
Internal current consumption
CS1W-HIO01-V1: 600 mA at 5 VDC
CS1W-HCP22-V1: 800 mA at 5 VDC
CS1W-HCA22-V1: 750 mA at 5 VDC, 150 mA at 26 VDC
CS1W-HCA12-V1: 750 mA at 5 VDC, 150 mA at 26 VDC
Dimensions 34.5
´
130
´
100.5 mm (W
´
H
´
D)
Weight
CS1W-HIO01-V1:
250 g max.
CS1W-HCP22-V1/HCA22-V1/HCA12-V1:
350 g max.
Standard accessories
CS1W-HIO01-V1
One OMRON C500-CE241 Connector Set for connecting to I/O
connector (soldered type; socket: FCN-361J024-AU made by
Fujitsu; connector cover: FCN-360C024-J2 made by Fujitsu)
CS1W-HCP22-V1/HCA22-V1/HCA12-V1
In addition to the above, one C500-CE404 Connector Set (made by
OMRON) for connecting to special I/O connector (soldered type;
socket: FCN-361J040-AU made by Fujitsu; connector cover: FCN-
360C040-J2 made by Fujitsu)
Item
Specifications
Control method
Stored program
I/O control method
Cyclic scan and immediate processing are both possible.
Customizable Counter Unit operating modes
RUN mode, MONITOR mode, PROGRAM mode
RUN/STOP specification method for Customiz-
able Counter Unit’s program
Select between the following:
1.
RUN/STOP commands from the CPU Unit’s allocated memory
2.
Operating mode command at startup, or command from the Pro-
gramming Device after startup
Status output to CPU Unit
Unit’s operating mode (RUN/STOP), fatal errors, CYCLE TIME OVER
errors, Unit error codes, etc.
Compatible Programming Devices
Programming Console (C200H-PRO27 or CQM1H-PRO01) or CX-
Programmer Ver. 1.2 or later (Specify CQM1H as the PLC type. There
are restrictions, such as the program capacity.)
Programming language
Ladder diagram
Execution modes
Possible to switch between Normal Execution Mode and High-speed
Execution Mode.
• Normal Execution Mode: 0.4
m
s for LD instruction
• High-speed Execution Mode: 0.2
m
s for LD instruction
Program capacity
4 Kwords (Normal Execution Mode)
Note
In High-speed Execution Mode, the capacity for which execu-
tion (compiling) is possible is restricted. Also, whether or not
programs can be executed depends on the contents of the pro-
gram. The average program capacity in High-speed Execution
Mode is approx. 1 Kword.
Instruction length
1 to 4 words per instruction
Number of instructions
113 (14 basic instructions and 99 special instructions)
Instruction exe-
cution time
Basic instructions
Normal Execution Mode: 0.4
m
s (LD instruction)
High-speed Execution Mode: 0.2
m
s (LD instruction)
Special instructions
Normal Execution Mode: 4.8
m
s (MOV instruction)
High-speed Execution Mode: 4.4
m
s (MOV instruction)
Item
Specification
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......