90
Details
Section 6-2
6-2-4
AR Area
AR bits are used for specific functions related to the operation of the Custom-
izable Counter Unit’s special I/O. For details on the functions of individual bits,
refer to
6-4 AR Area.
6-2-5
LR Area
This area can be used for data exchange with user-set words (in the CIO, WR,
AR, HR, DM, or EM Area) in the CPU Unit.
The words used in the CPU Unit are set in the Unit Setup Area (DM 6601 to
DM 6604) as shown below. The input and output areas in the LR Area are
allocated in the order input area
®
output area starting from the first word of
the LR Area. The number of words in the areas are determined by the refresh
settings.
General-purpose I/O is exchanged between the LR Area and the user-set
words in the CPU Unit, as shown in the following table.
Note
When LR Area bits are not being used for the above functions, they can be
used as work bits.
Customizable Counter Unit
CPU Unit
LR 00
First word
of output
area
LR Area
Output area
Unused words
User-defined
address
User-defined
address
General-purpose area
General-purpose
output area
General-purpose
input area
Number of re-
freshed words
in output area
Number of re-
freshed words
in input area
Input area
Number of re-
freshed words
in input area
Number of re-
freshed words
in output area
Address
Bits
Function
Contents
DM 6601
00 to 07
Input area (input from the CPU
Unit to the Customizable
Counter Unit)
Number of refreshed words
00 (BCD): Not refreshed
01 to 32 (BCD): 1 to 32 words
08 to 15
CPU Unit area
00 (BCD): CIO
01 (BCD): WR
02 (BCD): AR
03 (BCD): HR
04 (BCD): DM
05 (BCD): EM
DM 6602
00 to 07
Output area (output from the
Customizable Counter Unit to
the CPU Unit)
Number of refreshed words
00 (BCD): Not refreshed
01 to 32 (BCD): 1 to 32 words
08 to 15
CPU Unit area
00 (BCD): CIO
01 (BCD): WR
02 (BCD): AR
03 (BCD): HR
04 (BCD): DM
05 (BCD): EM
DM 6603
00 to 15
Input area
First word in CPU Unit area
0000 to 9999 (BCD)
DM 6604
00 to 15
Output area
First word in CPU Unit area
0000 to 9999 (BCD)
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......