Locating and Correcting Cable Disconnections
Section 10-4
• Sends the 06 06 FINS command to all Communications Units (except the
local node) in the local network.
• Sets the control data.
• Sends the 06 06 FINS command to the Communications Unit at the local
node in the local network.
Note When using the sample program as written above, be sure that the bits and
words in the sample program are not already being used by the program or
other Special Units.
10-4-5 Reading the Ring Status
It is necessary to know the structure of the ring status word when displaying
the word on a Programmable Terminal or other device because several pieces
of information are combined in the ring status word. In particular, the “node
address of disconnected node” is stored in hexadecimal and mixed with other
status flags, so the node addresses must be extracted and converted to deci-
mal.
The sample programs shown below read the two “node address of discon-
nected node” addresses and store these addresses in the DM area in BCD
format. In this example, the Controller Link Unit’s unit number is 0.
Structure of the Ring
Status Word
The following diagram shows the structure of the ring status word.
DM word
Contents
Function
D00000
00
02
Number of bytes of command data = 2 bytes
D00001
00
04
Number of bytes of response data = 4 bytes
D00002
00
00
Destination network address = 0 (the local network)
D00003
00
FE
Destination node address = 00 (local node)
Destination unit address = FE (Communications Unit)
D00004
07
02
Response required,
Transmission port number = 7,
Number of retries = 2
D00005
00
64
Response monitoring time = 10 s
Node address of disconnected node (hexadecimal, 2 digits)
(00 Hex: No disconnected nodes detected.)
Disconnected Interface Flag
0: SL1 (uplink) or normal status
1: SL2 (downlink)
Disconnected node
information #2
(See note.)
Local Node Disconnection Flag
0: Normal
1: Disconnection detected
Node address of disconnected node (hexadecimal, 2 digits)
(00 Hex: No disconnected nodes detected.)
Disconnected Interface Flag
0: SL1 (uplink) or normal status
1: SL2 (uplink)
Disconnected node
information #1
(See note.)
Network Disconnection Flag
0: Normal
1: Disconnection detected
Note The disconnected node information is valid only when bit 15 (the Network
Disconnection Flag) is ON. If bit 15 is OFF, the earlier disconnected node
information is retained.
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...