181
Memory Areas Related to Duplex Operation
Section 8-6
Note Duplex Communications Switch Cause Flags (A042 to A049)
8-6-2
PLC Setup
The Duplex Unit settings (the checkboxes for unit numbers 0 to 15 under
Communication Unit Duplex Setting in the CX-Programmer) can be set with
the addresses given below.
Note Duplex settings for Communications Units in the PLC Setup can be performed
with CX-Programmer Ver. 3.0 or later.
15
8 7
0
A042
Unit number 1
Unit number 0
The following error codes are written to
the corresponding area for each unit
number.
01 Hex: EEPROM error
02 Hex: Error in the communications
controller’s transmitter
03 Hex: Hardware error in the
communications controller
80 Hex: Watchdog timer error
A043
Unit number 3
Unit number 2
A044
Unit number 5
Unit number 4
A045
Unit number 7
Unit number 6
A046
Unit number 9
Unit number 8
A047
Unit number 11
Unit number 10
A048
Unit number 13
Unit number 12
A049
Unit number 15
Unit number 14
Address in
Programming
Console
Settings
Function
New setting’s
effectiveness
Word
Bits
121
0 to 15
0: Disable duplex
settings for Com-
munications Units
1: Enable duplex
settings for Com-
munications Units
Default: 0
These settings (individual bits)
enable or disable duplex set-
tings for individual Communi-
cations Units. Bits 00 to 15
correspond to unit numbers 0
to 15.
Active/standby can be speci-
fied by selecting the slot with
the standby Unit using the I/O
table editing operations from
the CX-Programmer.
At power-ON
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...