96
Setting Data Links
Section 5-2
CVM1 or CV-series Startup Node
Set the following DM parameter area settings in the PLC that is the startup
node.
Settings
Data link mode
Set to 01 for automatic setting.
(00 is for manual setting. Other values are invalid.)
Area 1 data link start word (BCD) *1
Area 1 type
Number of send words per node of Area 1 (BCD)
Rightmost 4 digits of data link start word of Area 2 (DM area) (BCD)
Leftmost digit of data link start word of
Area 2 (BCD)
First data link status word (BCD)
-: Not used.
*1: BCD: Set the value as binary-coded decimal.
*2: With Optical Bus (CLK11) Optical Link Units, N+10 and N+11 (node addresses 33 to 62) cannot be used.
Nodes to participate in the data links (*2)
The numbers indicate node numbers.
The value assigned indicates whether the
node is to participate in the data links.
Participate: 1
Not participate: 0
Word N
0:
Always specify 0.
-:
Other settings
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
15
8
7
0
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
N+1
N+2
N+3
N+4
N+5
N+6
N+7
N+8
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
N+9
-
-
0
0
0
0
0
0
0
0
-
N: DM 2000 + 100 Controller Link Unit number
Area 2 type
Number of send words per node of Area 2 (BCD)
00
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
N+10
-
-
62 61 60 59 58 57 56 55 54 53 52 51 50 49
N+11
-
-
-
Item
Setting range
Data link mode
Specify automatic (01).
Area 1 data link start
word
Set the word address in BCD.
CIO Area: CIO 0000 to CIO 2555
LR Area: LR 000 to LR 199 (*)
*: When a word between LR 000 and LR 199 is specified, the
data link area will be allocated between CIO 1000 and
CIO 1199.
Area 1 type
Set the area for Area 1 in BCD.
CIO Area: 80 Hex
LR Area: 86 Hex
Area 1 not used: 00 Hex
Number of send words
per node of Area 1
Set the number of words in BCD between 0 and 1,000.
The total number of send words of Area 1 and Area 2 must
not exceed 1,000.
When Area 1 is not used, set to 0.
Area 2 data link start
word
Set the word address in BCD.
DM Area: DM 0000 to DM 8191
(CV500/CVM1-CPU01)
DM 0000 to DM 24575 (Other CPU Units)
EM Area:
Banks 00 to 07, EM 0000 to EM 32765
(EM must be installed)
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...