74
Wiring and Connections
Section 3-4
Using Pulse Outputs
The following diagrams show example applications of sink-type transistor out-
puts using output bits IR 01000 and IR 01001. Use the PULS(65), SPED(––),
ACC(––), PWM(––), and SYNC(––) instructions to produce pulse outputs
(rather than normal outputs) from output bits IR 01000 and IR 01001.
Note
*CW is clockwise and CCW is counter-clockwise.
Output Wiring Precautions
Observe the following precautions to protect the PC’s internal components.
Output Short Protection
The output or internal circuitry might be damaged when the load connected to
an output is short-circuited, so it is recommended to install a protective fuse in
each output circuit.
Inductive Loads
When connecting an inductive load to an input, connect a surge protector or
diode in parallel with the load.
CPM2C-S
Single-phase pulse output
(Fixed duty ratio)
Motor driver
Pulse output 0:
01000
CPM2C-S
Pulse output 1:
01001
COM
Motor driver
Single-phase pulse output
(Variable duty ratio)
Relay
Pulse output 0:
01000
CPM2C-S
Pulse output 1:
01001
COM
Relay
Pulse plus direction output
Motor driver
Pulse output 0:
01000
CPM2C-S
Direction output:
01001
COM
Direction
input
Increment pulse output
Motor driver
CW* pulse output:
01000
CCW* pulse output:
01001
COM
CW input
CCW input
24 V
24 V
24 V
24 V
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......