206
Programming Console Operation Errors
Section 9-3
9-2-5
Fatal Errors
PC operation and program execution will stop and all outputs from the PC will
be turned OFF when any of these errors have occurred. CPM2C-S operation
can’t be restarted until the PC is turned OFF and then ON again or a Pro-
gramming Device is used to switch the PC to PROGRAM mode and clear the
fatal error.
All CPU Unit indicators will be OFF for the power interruption error. For all
other fatal operating errors, the POWER and ERR/ALM indicators will be lit.
The RUN indicator will be OFF.
9-3
Programming Console Operation Errors
The following error messages may appear when performing operations on the
Programming Console. Correct the error as indicated and continue operation.
Note
Refer to the relevant Support Software Operation Manual for details on errors
that may appear when operating the SSS or SYSMAC-CPT Support Soft-
ware.
Message
FALS
No.
Meaning and appropriate response
Power interruption
(no message)
None
Power has been interrupted for more than 10 ms (2 ms for DC power types.)
Check power supply voltage and power lines. Try to power-up again.
MEMORY ERR
F1
AR 1308 ON: There is a non-existent bit or word address in the user program. Check the
program and correct errors.
AR 1309 ON: An error has occurred in flash memory. Replace the CPU Unit.
AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599).
Check and correct the settings in the read-only DM area.
AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize the PC Setup
and input the settings again.
AR 1312 ON: A checksum error has occurred in the program. Check the program and
correct any errors detected.
AR 1313 ON: A checksum error has occurred in the expansion instructions data and all
function codes have been set the their default values. Reset the expansion instructions.
AR 1314 ON: Data was not maintained in an area specified for holding. Clear the error,
check the data in the areas specified for holding, and try again.
AR 1315 ON: A CompoBus/S Master ASIC error occurred. Replace the CPM2C-S.
NO END INST
F0
END(01) is not written in the program. Write END(01) at the end of the program.
I/O BUS ERR
C0
An error has occurred during data transfer between the CPU Unit and an Expansion I/O
Unit or Expansion Unit. Check the Unit’s connecting cable.
I/O UNIT OVER
E1
Too many Expansion Units or Expansion I/O Units (more than 5) have been connected.
Check the Unit configuration. Do not connect more than 3 Expansion Units or Expansion
I/O Units.
SYS FAIL FALS**
(** is 01 to 99 or 9F.)
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to
determine the conditions that caused execution, correct the cause, and clear the error.
9F
The cycle time has exceeded the Maximum (Watch) Cycle Time setting (DM 6618).
Check the cycle time and adjust the Maximum Cycle Time setting if necessary.
Message
Meaning and appropriate response
REPL ROM
An attempt was made to write to write-protected memory. Set bits 00
to 03 of DM 6602 to “0.”
PROG OVER
The instruction at the last address in memory is not NOP(00). Erase
all unnecessary instructions after END(01).
ADDR OVER
An address was set that is larger than the highest memory address
in Program Memory. Input a smaller address.
SETDATA
ERR
FALS 00 has been input, and “00” cannot be input. Reinput the data.
I/O NO. ERR
A data area address has been designated that exceeds the limit of
the data area, e.g., an address is too large. Confirm the requirements
for the instruction and re-enter the address.
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......