126
Explicit Message Communications
Section 6-3
Instance ID (command)
Specify the data area containing the desired data in 1 byte (2-digit hexadeci-
mal). Use one of the codes listed in the following table.
Address L and Address H (command)
Specify the starting word address of the read data in hexadecimal as follows:
Address L: The rightmost two digits of the 4-digit starting address.
Address H: The leftmost two digits of the 4-digit starting address.
Number of words (command)
Specify the number of words of data to read in 1 byte (2-digit hexadecimal).
The allowed range is 01 to 64 (Hex), which is equivalent to 1 to 100 decimal.
Number of bytes received (response)
Indicates the number of bytes of data (in hexadecimal) from the “source node
number.”
Source node number (response)
Indicates the node number (in hexadecimal) of the CPM2C-S that returned
the response.
Read data (response)
Contains the desired data read from the specified data area. Word data is
returned with the leftmost byte (bits 8 to 15) preceding the rightmost byte (bits
0 to 7).
Precautions
The range of data specified by the data area (instance ID), starting address
(Address L and Address H), and number of words parameters must not
exceed the range of the CPM2C-S data area.
WRITE WORD DATA
Writes data from the DeviceNet Master to the specified node’s data area in
word-units (two-byte units). When word data is being written, the leftmost byte
is written before the rightmost byte. Up to 100 words can be written at one
time.
Command Format
Code
Area name
Address range
01 (Hex)
IR area
IR 000 to IR 049
02 (Hex)
IR area
IR 200 to IR 227
03 (Hex)
DM area
DM 0000 to DM 2047
04 (Hex)
LR area
LR 00 to LR 15
05 (Hex)
HR area
HR 00 to HR 19
06 (Hex)
AR area
AR 00 to AR 23 (read area only)
07 (Hex)
Timer/Counter area
TC 000 to TC 255
Destination node number
Service code
Class ID
Instance ID
Address L
Address H
Leftmost
byte
Rightmost byte
Write data
(200 bytes max.)
Leftmost byte
Rightmost byte
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......