High-speed Counters
Section 7-1
7-1-2
High-speed Counter Specifications
Specifications
Item
Specification
Number of high-speed counters
2 (High-speed counters 0 and 1)
4 (High-speed
counters 0 to 3)
Pulse input modes (Selected in the PLC
Setup)
Differential phase
inputs
Up/down inputs
Pulse + direction
inputs
Increment inputs
Input terminal allocation
Phase-A input
Increment pulse
input
Pulse input
Increment pulse
input
Phase-B input
Decrement pulse
input
Direction input
---
Phase-Z input
Reset input
Reset input
Reset input
Input method
Differential phase,
4x
(Fixed)
Two single-phase
inputs
Single-phase
pulse + direction
inputs
Single-phase
input
Response frequency
50 kHz
100 kHz
100 kHz
100 kHz
Counting mode
Linear mode or circular (ring) mode (Select in the PLC Setup.)
Count values
Linear mode: 8000 0000 to 7FFF FFFF hex
Ring mode: 0000 0000 to Ring SV
(The Ring SV (Circular Max. Count) is set in the PLC Setup and the setting
range is 00000001 to FFFFFFFF hex.)
High-speed counter PV storage locations
High-speed counter 0: A271 (leftmost 4 digits) and A270 (rightmost 4 digits)
High-speed counter 1: A273 (leftmost 4 digits) and A272 (rightmost 4 digits)
High-speed counter 2: A317 (leftmost 4 digits) and A316 (rightmost 4 digits)
High-speed counter 3: A319 (leftmost 4 digits) and A318 (rightmost 4 digits)
Target value comparison interrupts or range comparison interrupts can be
executed based on these PVs.
Note
The PVs are refreshed in the overseeing processes at the start of each
cycle. Use PRV(881) to read the most recent PVs.
Data format: 8 digit hexadecimal
Range in linear mode: 8000 0000 to 7FFF FFFF hex
Range in ring mode: 0000 0000 to Ring SV (Circular Max. Count)
Control
method
Target value comparison
Up to 48 target values and corresponding interrupt task numbers can be reg-
istered.
Range comparison
Up to 8 ranges can be registered, with a separate upper limit, lower limit, and
interrupt task number for each range.
Counter reset method
Select one of the following methods in the PLC Setup.
•Phase-Z + Software reset
The counter is reset when the phase-Z input goes ON while the Reset Bit is
ON.
•Software reset
The counter is reset when the Reset Bit goes ON.
(Set the counter reset method in the PLC Setup.)
Note
Operation can be set to stop or continue the comparison operation
when the high-speed counter is reset.
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......