94
Sec
tion 5
App
e
ndic
e
s
E3NW-CRT
User’s Manual
Section 5
Command Response Time (Reference Values)
Command Response Time (Reference Values)
The time required from when a command is sent to obtain the incident light level of input 1
of Sensor Amplifier Unit 1 connected to an E3NW-CRT Communications Unit until a
response is received is approximately 6 ms. (when an explicit message is used).
* The command response time is a reference value only. Perform thorough testing in your
own environment before use.
Command response time = (1)
Test conditions
Baud rate: 4 Mbps
CPU Unit cycle time: 1 ms
Number of CompoNet Slave Units: 1
●
Communications Configuration
●
Executed Command
Item
Model number
Version
CPU Unit
NJ301-1100
Version 1.02
CompoNet Master Unit
CJ1W-CRM21
Version 1.3
CompoNet Slave Unit
E3NW-CRT
Sensor Amplifier Unit
E3NW-FA0
ServiceCode
0E
ClassID
9F
InstanceID
03
AttributeID
82
1
PLC
Sensor Amplifier Unit
CompoNet Unit
Communications
Unit