
16
EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications
Section 2-1
CJ2 CPU Built-in EtherNet/IP Port
Note
If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can
be used, but this is not recommended.
Item
Specifications
Model number
CJ2H-CPU
@@
-EIP
CJ2M-CPU3
@
Type
100Base-TX (See note.)
Unit classification
CJ2 CPU Unit built-in port (CJ2 CPU Bus Unit)
CPU Unit
words used
Allocated CIO Area
words (CPU Bus
Unit words)
25 words/Unit (one unit number’s words)
These words contain control bits and flags, the target node PLC’s operating and error
information, Unit status, communications status, registered/normal target node infor-
mation, and FINS/TCP connection status.
Allocated DM Area
words (CPU Bus
Unit words)
100 words/Unit (one unit number’s words)
These words contain the IP address display/setting area.
User-set area
Any usable data area words
Target node PLC’s operating and error information, and registered/normal target
node information
CPU Bus Unit Sys-
tem Setup
Not used.
Non-volatile memory for the CJ2
built-in EtherNet/IP port
The following settings are stored in the non-volatile memory for the built-in EtherNet/
IP port.
Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU
Unit is not used for these settings.
1. Unit Setup (communications settings for the built-in EtherNet/IP port, such as the
IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and
FINS/TCP settings)
2. Tag data link settings (device parameters)
Transfer
specifica-
tions
Media access
method
CSMA/CD
Modulation method
Baseband
Transmission paths
Star form
Baud rate
100 Mbit/s (100Base-TX)
Transmission media
Shielded twisted-pair (STP) cable
Categories: 100
Ω
at 5, 5e
Transmission dis-
tance
100 m (distance between hub and node)
Number of cascade
connections
There is no limitation when a switching hub is used.
Current consumption (Unit)
For CJ2 CPU Units, refer to the CJ2 CPU Hardware Operation Manual (W472).
Weight
Dimensions
Other general specifications
Other specifications conform to the general specifications of the CJ2 or built-in Ether-
Net/IP port CJ2 CPU Unit.
Содержание CJ2H-CPU6 - REV 02-2010
Страница 2: ......
Страница 4: ...iv...
Страница 6: ...vi...
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 38: ...12 Network Configurator Overview Section 1 5...
Страница 58: ...32 Selecting the Network Devices Section 2 3...
Страница 116: ...90 Auxiliary Area Data Section 4 5...
Страница 222: ...196 Message Communications Errors Section 7 6...
Страница 364: ...338 Using the Backup Tool Section 13 3...
Страница 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Страница 404: ...378 Ethernet Network Parameters Appendix B...
Страница 406: ...380 TCP Status Transitions Appendix C...
Страница 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Страница 460: ...434 Index...
Страница 462: ...436 Revision History...
Страница 463: ......