9-51
9 Troubleshooting and Maintenance
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-5 Even
t L
ogs
9
9-5-3 Error De
scr
iptio
ns
Event name
Overrun Error, Framing Error, or Parity Error (Transmis-
sion Error)
Event code
846C 0000 hex
Meaning
An overrun error, framing error, or parity error occurred.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
During Modbus-
RTU Slave Mode
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The communications conditions and
baud rate settings do not match the
host.
Review the system settings, host set-
tings, and programming, including the
command format and response for-
mat, based on *_P1_TransErrSta and
*_P2_TransErrSta (Transmission
Error Status).
Perform countermeasures in
advance.
Noise or other external interference.
•
Use shielded twisted-pair cables for
the communications cables.
•
Wire the communications cables in
separate ducts from power lines.
•
Check the environment for noise.
•
If required, perform retry processing
for communications.
The baud rate is outside the allowable
range or there are bit errors due to dif-
ferent stop bit settings or other
parameters.
•
Review the system settings.
•
Review the baud rate and other
host settings, and the programming,
including the command format and
response format.
•
The communications cable wiring is
faulty.
•
Terminating resistance is not set
correctly for the RS-422A/485 ports.
•
Wiring is faulty or terminating resis-
tance is not set correctly on an NT-
AL001 or other Adapter.
•
Check the communications cable
connections.
•
Turn ON the terminating resistance
(with the terminating resistance
ON/OFF switch) at both ends (at
the host).
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
You can check the number of transmission errors (i.e., overrun errors, framing errors, and parity errors) in the
*_P1_MbsTxErrCnt and *_P2_MbsTxErrCnt device variables.
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...