9 Troubleshooting and Maintenance
9-46
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event name
Comparison Error
Event code
64A5 0000 hex
Meaning
A comparison error occurred.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
During Loopback
Test
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
Loopback test jig failure.
Correct any mistakes in wiring the
loopback test jig.
Check the wiring of the loopback test
jig.
Noise
Implement noise countermeasures.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
The communications circuits in the
Serial Communications Unit are
faulty.
Replace the Unit.
None
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Event name
Reception Overflow
Event code
64A6 0000 hex
Meaning
More than the specified amount of receive data was received in No-protocol Mode.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
During No-proto-
col Mode
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
One or more bytes of data was
received after the completion the
reception.
Execute the SerialRcv/SerialRcvNo-
Clear instruction again after the
Reception Completed Flag changes
to TRUE.
Review the communications period
with the remote device.
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...