9 Troubleshooting and Maintenance
9-28
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-4-3
Error Codes and Troubleshooting
Error
code
Troubleshooting
Serial communications mode
Protocol
Macro
Serial
Gateway
No-
protocol
Loop-
back Test
Modbus-
RTU
Slave
0001 Hex
Replace the CPU Unit.
Yes
Yes
Yes
Yes
Yes
0002 Hex
Check the operating environment.
Yes
Yes
Yes
Yes
Yes
0006 Hex
Check the unit number setting.
Recreate the Unit Configuration.
Yes
Yes
Yes
Yes
Yes
000F Hex
Check the operating environment.
Yes
Yes
Yes
Yes
Yes
0011 Hex
Check the operating environment.
Yes
Yes
Yes
Yes
Yes
0012 Hex
Check the relevant data.
Yes
Yes
Yes
Yes
Yes
0014 Hex
Check the operating environment.
Yes
Yes
Yes
Yes
Yes
0108 Hex
Check the unit number setting.
Yes
Yes
Yes
Yes
Yes
010B Hex
Refer to the CPU Unit's operation manual to
eliminate the cause of the error.
If the error persists, replace the CPU Unit.
Yes
Yes
Yes
Yes
Yes
010D Hex Set the destination address in the routing tables.
Yes
Yes
Yes
Yes
Yes
010E Hex
Set the destination address in the routing tables.
Yes
Yes
Yes
Yes
Yes
0112 Hex
Make sure to use the command addresses.
No
No
No
No
No
0117 Hex
Increase the number of retries or correct the sys-
tem so that communications do not jam.
Yes
Yes
Yes
Yes
Yes
0118 Hex
Check whether there is a node sending irregular
data.
Yes
No
Yes
Yes
Yes
011B Hex
Correct the transmission method and baud rate
settings.
Check for noise interference.
No
Yes
Yes
No
Yes
011C Hex Correct the transmission method and baud rate
settings.
Check for noise interference.
No
Yes
Yes
No
Yes
011D Hex Correct the transmission method and baud rate
settings.
No
Yes
Yes
No
Yes
011E Hex
Correct the transmission method and baud rate
settings.
Check for noise interference.
Check whether the FCS calculation method is
correct.
No
Yes
No
No
Yes
021A Hex
Reset the relevant table.
Yes
Yes
Yes
Yes
Yes
0300 Hex
Conduct a loopback test, and eliminate the
cause of the error.
Yes
Yes
Yes
Yes
Yes
0301 Hex
Refer to the Remedy for Each Protocol Macro
Error Code on page 9-21 to eliminate the cause
of the error.
Yes
No
No
No
No
0302 Hex
A new command is received during command
processing. Correct the applications at the host
computer.
No
No
No
No
No
0601 Hex
Check the operating environment.
Yes
Yes
Yes
Yes
Yes
0602 Hex
Depending on the error details, delete the error
log and transfer protocol macro data. If the error
persists, replace the Unit.
Yes
Yes
Yes
Yes
Yes
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...