7-15
7 Using Modbus-RTU Slave Mode
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
7-3 Co
mm
and
and
Resp
onse
Detail
s
7
7-3
-2 Comma
nd and Response Det
ails
z
Function
Reads multiple bits from the CIO Area of the memory used for CJ-series Unit.
z
Command
z
Response
* N=Quantity of Registers
z
Reading 19 Bits from CIO 0001.04 to CIO 0002.06
Note
Unused bits are filled with zeros.
Note
The subscript numbers in the shaded boxes indicate the TRUE/FALSE (1/0) status of the bits
that are read.
Read Discrete Inputs
Length
Data
Function Code
1 byte
02 hex
Starting Address
2 bytes
0000 to 13FF hex
Quantity of Coils
2 bytes
0001 to 03E8 hex (1 to 1000)
Length
Data
Function Code
1 byte
02 hex
Byte Count
1 byte
N (*)
Coil Status
n byte
n = N or N+1
Request
Response
Data
Data
Function Code
02 hex
Function Code
02 hex
Starting Address (H)
00 hex
Byte Count
03 hex
Starting Address (L)
14 hex
Coil Status 27 to 20
CD hex
Quantity of Coils (H)
00 hex
Coil Status 35 to 28
6B hex
Quantity of Coils (L)
13 hex
Coil Status 38 to 36
05 hex
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CIO 0
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CIO 1
31
1
30
0
29
1
28
1
27
1
26
1
25
0
24
0
23
1
22
1
21
0
20
1
19
18
17
16
CIO 2
47
46
45
44
43
42
41
40
39
38
1
37
0
36
1
35
0
34
1
33
1
32
0
CIO 3
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...