6 No-protocol Mode
6-6
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
*_P1_ParityYNCfg
*_P2_ParityYNCfg
BOOL
RW
Parity (Yes/No)
FALSE: Yes
TRUE: No
Default: FALSE
*_P1_ParityBitCfg
*_P2_ParityBitCfg
BOOL
RW
Parity
(Even/Odd)
FALSE: Even
TRUE: Odd
Default: FALSE
*_P1_BaudrateCfg
*_P2_BaudrateCfg
USINT
RW
Baud Rate
(unit: bps)
0: 9600 3: 1200 4: 2400
5: 4800 6: 9600 7: 19200
8: 38400 9: 57600
10: 115200
11: 230400
Default: 0
*_P1_SendDelayCfg
*_P2_SendDelayCfg
WORD
RW
Send Delay
Setting
Bit 15: Send delay time
Bits 00 to 14: Send delay
setting range
*_P1_SendDelaySetCf
g
*_P2_SendDelaySetCf
g
BOOL
RW
Send Delay
Time
FALSE: Default (0 ms)
TRUE: User settings
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you configure
this setting, set to bits
00 to 14 of
*_P1_SendDelayCfg.
There is no specific
device variable for CJ-
series Unit to reference
the send delay setting
range.
When you configure
this setting, set to bits
00 to 14 of
*_P2_SendDelayCfg.
Bit
string
RW
Send delay set-
ting range
0 to 300 s (0 to 300,000
ms)
(0000 to 7530 hex; 0 to
30,000 decimal) [Unit: 10
ms]
*_P1_HlkCTSCtlCfg
*_P2_HlkCTSCtlCfg
BOOL
RW
CTS Control
(*2)
FALSE: No
TRUE: Yes
Default: FALSE
*_P1_NopStartCodeCfg
*_P2_NopStartCodeCfg
USINT
RW
No-protocol
Start Code
Range: 0 to 255
*_P1_NopEndCodeCfg
*_P2_NopEndCodeCfg
USINT
RW
No-protocol
End Code
Range: 0 to 255
*_P1_NopCfg
*_P2_NopCfg
WORD
RW
No-protocol
Settings
Bit 12: No-protocol start
code inclusion setting
Bit 09: No-protocol CR +
LF specification setting
Bit 08: No-protocol end
code inclusion setting
Bits 00 to 07: Number of
received data bytes in No-
protocol Mode
*_P1_NopStartCodeY
NCfg
*_P2_NopStartCodeY
NCfg
BOOL
RW
No-protocol
Start Code
Inclusion Set-
ting
TRUE: Yes
FALSE: No (default)
Device variable for CJ-series Unit
Type
R/W
Name
Function
Port 1
Port 2
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...