m
The CIO and DM number occupied by the PROFIBUS Slave Unit are set by the
machine number rotary switch on the front of the Unit.
Allocated CIO words (Start address CIO Area = 2000 + MACH No. x 10)
Allocated DM words (Start address DM Area = 20000 + MACH No. x 100):
Additional Information
•
If two or more Units are set to an identical Machine number or if one Unit is set to areas of plu-
ral Machine numbers, the CPU Unit has a major fault level error, a duplicated Unit number
error, and stops operation. After correcting the Machine number setting, cycle the power to the
Controller.
•
Be sure that no Machine numbers are duplicated.
To avoid duplication, when you set a PROFIBUS Slave Unit to the Machine number "n", set the
next Unit to the Machine number "n + 1".
MACH No.
CIO Area
MACH No.
CIO Area
00
CIO 2000 to CIO 2009
06
CIO 2060 to CIO 2069
01
CIO 2010 to CIO 2019
07
CIO 2070 to CIO 2079
02
CIO 2020 to CIO 2029
08
CIO 2080 to CIO 2089
03
CIO 2030 to CIO 2039
09
CIO 2090 to CIO 2099
04
CIO 2040 to CIO 2049
10..
CIO 2100 to CIO 2109
05
CIO 2050 to CIO 2059
..95
CIO 2940 to CIO 2949
MACH No.
CIO Area
MACH No.
CIO Area
00
DM 20000 to DM 20007
06
DM 20600 to DM 20607
01
DM 20100 to DM 20107
07
DM 20700 to DM 20707
02
DM 20200 to DM 20207
08
DM 20800 to DM 20807
03
DM 20300 to DM 20307
09
DM 20900 to DM 20907
04
DM 20400 to DM 20407
10
DM 21000 to DM 21007
05
DM 20500 to DM 20507
95
DM 29500 to DM 29507