37
Network Installation
Section 3-6
3-6-4
Noise Reduction when Using Contact Outputs
Communications errors can occur when Contact Output Units are mounted to
the same Rack or connected to the same PLC as an FL-net Unit due to noise
generated by the contact outputs. Use one or more of the following measures
when installing Contact Output Units and Ethernet Units on the same Rack.
Mounting Location
Mount (or connect) any Contact Output Units as far away from the FL-net Unit
as possible.
Cable Location
Separate the transceiver cable or twisted-pair cable connecting the FL-net
Unit as far from the wiring to the Contact Output Units as possible. The coax-
ial cable must also be placed as far away from the Contact Output Units and
their wiring as possible.
Contact Output Unit
FL-net Unit
Contact outputs
Contact Output Unit
FL-net Unit
Contact outputs
To transceiver/hub
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...