181
Operating Procedures
Section 11-2
11-2-8 Unit Area Setup
The Unit's data display and node name can be set.
Note
Select
Option - Switch display - Hex
. It will be possible to display and input
in hexadecimal.
11-2-9 Monitor Status Display Function
The CX-FLnet enables monitoring of various network conditions and settings.
■
Selecting the Status Display Function
Select the status from among those displayed in the Status Menu in the Main
Menu.
Menu
Function
Allowed min. frame interval
(default: 1 (100 us))
Sets the present minimum allowable frame interval.
Valid
must be selected to enable
this setting. If communications errors occur, increase the value of this setting. The
maximum allowable frame interval used for the entire network is that of the node with
the longest minimum allowable frame interval. The present valid value for the net-
work can be checked by selecting
Network status (FA Link)
in the
Monitor
Field.
When a baud rate of 100 Mbps is used, set the minimum allowable frame interval to
1 ms or higher.
Token watchdog timer
(default: 50 ms)
Sets the timeout time for monitoring token passing between nodes. For normal
usage, use the default value.
Wait time of min. frame interval
(default: 0)
Adds the value set here to the minimum allowable frame interval set in (1). This value
is not used by the entire network. This value is only enabled for the corresponding
node.
Node name
Sets the node name.
Valid
must be selected to enable this setting.
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...