Error Log
Section 10-3
150
Error Log Table
Each error is recorded as one record in an error log table. Up to 64 records
can be saved. If more than 64 errors occur, the oldest errors will be deleted
from the error log and the most recent error will be recorded.
The following information is recorded in the error log table.
• Main error code (See table later in this section.)
• Detailed error code (See table later in this section.)
• Time stamp (from the clock in the CPU Unit)
Error Log Location
When an error is detected, the error codes and time stamp are recorded in the
error log in RAM inside the FL-net Unit. Serious errors are also recorded in
EEPROM. The maximum number of errors that can be saved to EEPROM is
32. The errors recorded in EEPROM will be saved even if the Unit is restarted
or power is turned OFF. When the FL-net Unit is started, the contents of the
error log in EEPROM are copied to RAM.
When a FINS command is used to read the error log, the log held in RAM is
read. The error log cannot be cleared.
FINS Commands for Error
Logs
The FL-net Unit’s error log can be read using the CX-FLnet or FL-net Unit
Support Software. The following FINS commands can also be used to read or
clear the error log. For details on each command, refer to
.
10-3-2 Error Log Error Codes
The error codes are described in the following table. The detailed error code
will provide detailed information on an error.
Command
code
Function
MRC
SRC
21
02
ERROR LOG READ
Error
code
Meaning
Detailed error code
Correction
EE-
PROM
1st byte
2nd byte
0001
Watchdog timer error in CPU Unit
00
00
Replace the CPU Unit.
Saved
0002
CPU Unit service monitor error
monitoring time (ms)
Check the operating environment. Saved
0006
Other CPU error
Bit 11: Unit not in Registered
I/O Tables
Create the I/O tables.
Saved
000F
CPU Unit initialization error
00
00
Replace the CPU Unit.
Saved
0010
Insufficient System Setup Area
00
00
Reduce the number of CPU Bus
Units.
Saved
0011
Event timed out
01: Read
error
02: Write
error
03: Routing
table
04: Setup
error
05: CPU Bus
Unit Words
(CIO/DM)
Replace the CPU Unit.
Saved
0012
CPU Unit memory error
01: Recreate the data specified by
the 2nd byte of the detailed error
code.
02: Clear memory using proce-
dure in the PLC operation manual.
Saved
0013
CPU Unit protected
00
00
Remove protection from CPU Unit
memory.
Saved
0040
Self-removal
Undefined
Check the communications cable
hub connection. Use the CX-
FLnet or FL-net Unit Support Soft-
ware to increase the value for the
minimum allowable frame interval.
---
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...