4 Remote I/O Master Communications
4-18
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Fixed Allocations Area 3
OUT blocks are allocated to slaves from CIO 3600 to CIO 3663 and IN blocks are allocated to slaves
from CIO 3700 to CIO 3763 in the memory used for CJ-series Unit. To access the output (OUT)
block and the input (IN) block from the user program, allocate a user-defined variable to the applica-
ble area.
The Slave allocation order is fixed in the output (OUT) and IN blocks that start from address 0. Each
address is allocated at least one byte (rightmost).
•
More than one word is allocated for each slave (according to it's node address) with more
than16 I/O points.
•
The rightmost byte of the word is allocated to each slave that has 8 I/O points or less.
The scan list must be cleared in the following situations:
•
Adding a slave
•
Disconnecting a slave
•
Changing a node address
Set the CPU Unit to PROGRAM Mode. Change
*_Sw1SListClrCmd
(Scan List Clear Switch) to TRUE
to clear the scan list. (Remote I/O communications will be performed with the scan list disabled using
fixed allocations in the fixed allocations area that was used the last time the list was disabled.)
Make sure that communications with all slaves are operating properly after the scan list is cleared and
the system component is changed, and then change
*_Sw1SListEnblCmd
(Scan List Enable Switch) to
TRUE again to register all slaves currently online in the scan list. Remote I/O communications will con-
tinue during this time with the scan list enabled.
4-3-3
Changing System Components
CIO Area in the memory for CJ-series Units
Bit
Bit
OUT block
IN block
OUT block
Bit
Address 0
IN block
Output to Slaves
Input from Slaves
Address 1
Address 2
Address 60
Address 61
Address 62
Address 63
Address 0
Address 1
Address 2
Address 60
Address 61
Address 62
Address 63
to
to
CIO 3600
to
CIO 3663
CIO 3700
to
CIO 3763
CIO 3600
CIO 3601
CIO 3602
CIO 3660
CIO 3661
CIO 3662
CIO 3663
CIO 3700
CIO 3701
CIO 3702
CIO 3760
CIO 3761
CIO 3762
CIO 3763
to
to
Содержание CJ1W-DRM21
Страница 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 214: ...6 Message Communications 6 26 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Страница 349: ......