3-27
3 Data Exchange with the CPU Unit
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
3-2
De
vice V
a
riab
les
f
o
r CJ-series
Unit (Software
S
w
itc
h
es, Statuses)
3
3-2-5 U
n
it Statu
s
1
Name of device variable for
CJ-series Unit
Type
R/W
Area
Function
*_SlavFunErr
BOOL
R
Slave Func-
tion Error
<Operation specifications>
TRUE:
Indicates that at least one slave error
occurred. Refer to
*_Slav1Sta
(Slave Sta-
tus 1).
The slave errors are as follows:
•
*_Slav1IO1Err
(Remote I/O Communi-
cations Error with slave communications
enabled, for OUT 1/IN 1)
•
*_Slav1IO2Err
(Remote I/O Communi-
cations Error with slave communications
enabled, for OUT 2/IN 2)
•
*_Slav1FunDatErr
(Invalid Setup Data)
•
*_Slav1IORefErr
(Slave I/O Refresh
Error)
FALSE:
Indicates that none of the above errors
occured. Or, changes to FALSE when all
of above errors are cleared.
Default: FALSE
*_MemErr
BOOL
R
Unit Mem-
ory Error
<Operation specifications>
TRUE:
Indicates an error in internal memory
where the error history is stored. (The
error occurs when the Unit starts up or
when the error history is written.)
FALSE:
Indicates that the error did not occur.
Once this error occurs, the bit will remain
TRUE and will not return to FALSE (Nor-
mal).
Default: FALSE
*_BusoffErr
BOOL
R
Bus Off
Error
<Operation specifications>
TRUE:
Indicates that a Bus OFF error (communi-
cations were stopped by multiple data
errors) occurred.
When a Bus OFF occurs, the Unit goes
offline and all communications stop
(remote I/O communications are stopped,
slave operation is stopped, and message
communications are disabled).
FALSE:
Indicates that the error did not occur.
Once this error occurred, the bit will
remain TRUE and will not return to FALSE
(Normal).
Default: FALSE
Содержание CJ1W-DRM21
Страница 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 214: ...6 Message Communications 6 26 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Страница 349: ......