Error codes
Section 5-2
98
5-2-6
System Errors
When errors occur in the CJ-series CPU Unit or on the I/O Bus the ERH-LED is
turned ON. At the occurrence of an I/O Bus error an error code (see n+17, n+18)
is generated as well.
Clearing System errors
Turn ON the power supply again or restart the system. If the error persists, then
replace the CJ-series CPU Unit.
Error Code 1
Error Code 2
Error
Description
000E
0000
I/O Bus error
An error has occurred on the I/O Bus causing the
Counter Unit to be in an undefined state. On
occurrence of an I/O Bus error you can configure the
Outputs to keep their last state or to have a pre-
defined state (refer to section 3-6
).
0002
Time-Out in
milliseconds
Time-Out error
A cyclic refresh time-out error was generated
caused by a PLC system error or you have chosen
to disable the Cyclic Refresh of the Counter Unit in
the CJ-series PLC settings. This error will be cleared
as soon as Cyclic Refresh will take place again. The
IORF ladder instruction has no influence on this
behaviour.