With the NJ Series, device variables for CJ-series Unit are used for the Counter Unit functions.
The following tables show how the words and bits of CJ-series I/O memory or the NJ-series memory
used for CJ-series Unit correspond to the NJ-series device variables for CJ-series Unit.
Start address of special I/O Unit area: n = 2000 words + Unit number
×
10 (Unit number: 0 to 92)
Start address of the special I/O Unit DM area: m = Unit number
×
100 (Unit number: 0 to 92)
Additional Information
• If two or more Special I/O Units are set to an identical Unit number or if one Special I/O Unit is
set to areas of plural Unit numbers, the CPU Unit has a major fault level error, a duplicated Unit
number error, and stops operation.
• After correcting the Unit number setting, cycle the power to the Controller.
• One High-speed Counter Unit occupies allocation areas of four Unit numbers. Be sure that no
Unit numbers are duplicated.
To avoid duplication, when you set a High-speed Counter Unit to the Unit number "n", set the
next Special I/O Unit to the Unit number "n + 4".
A-1-2
Differences in Access Methods from a User Program
The relay number and DM number occupied by the High-speed Counter Unit are set by the
Unit number switch on the front panel of the Unit.
One High-speed Counter Unit occupies allocation areas of four Unit numbers.
Unit Number
CIO Area words allocated to
Special I/O Unit
DM Area words allocated to
Special I/O Unit
0
0
2000 to 2039 words
D20000 to D20399 words
1
1
2010 to 2049 words
D20100 to D20499 words
2
2
2020 to 2059 words
D20200 to D20599 words
3
3
2030 to 2069 words
D20300 to D20699 words
4
4
2040 to 2079 words
D20400 to D20799 words
5
5
2050 to 2089 words
D20500 to D20899 words
6
6
2060 to 2099 words
D20600 to D20999 words
7
7
2070 to 2109 words
D20700 to D21009 words
8
8
2080 to 2119 words
D20800 to D21199 words
9
9
2090 to 2129 words
D20900 to D21299 words
10
10
2100 to 2139 words
D21000 to D21399 words
··
·
··
·
···
···
n
n
2000 + (n
×
10) to
2000 + (n
×
10) + 39
(n
×
100) to
(n
×
100) + 399
··
·
··
·
···
···
92
92
2920 to 2959 words
D29200 to D29599 words
93
(Cannot be set)
---
---
94
(Cannot be set)
---
---
95
(Cannot be set)
---
---
MACH
No.
X10
1
98
76
54
3
X10
0
98
76
54
3
Содержание CJ1W-CT021
Страница 10: ...Manual Structure 8 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 38: ...Revision History 36 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 190: ...Appendicies A 18 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492...
Страница 191: ...Index 1 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 I Index...
Страница 194: ...Index 4 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit W492 Index...
Страница 195: ......