311
Exchanging Data with the CPU Unit
Section 7-5
7-5-4
Special I/O Unit Restart Bits
To restart the Unit operations after changing the contents of the data memory
or correcting an error, turn ON the power to the PLC again or turn the Special
I/O Unit Restart Bit ON and then OFF again.
Note
If the error is not corrected by restarting the Unit or turning the Special I/O
Unit Restart Bit ON and then OFF again, replace the Analog I/O Unit.
Special I/O Unit
Area word
address
Function
A50200
Unit No. 0 Restart Bit
Restarts the Unit when turned
ON and then OFF again.
A50201
Unit No. 1 Restart Bit
~
~
A50215
Unit No. 15 Restart Bit
A50300
Unit No. 16 Restart Bit
~
~
A50715
Unit No. 95 Restart Bit